Line distance protection REL670 2.2 ANSI
Application manual
Unblock
Disabled
Set
=
(Set to
used.
Set to
tSecurity
Set
= 0.035 s
Set
DeltaI
= 10 %IB
DeltaV
Set
= 5 %VB
Delta3I0
Set
= 10 %IB
Delta3V0
Set
= 5 %VB

Permissive underreaching scheme

Operation
Enabled
Set
=
Set
SchemeType
=
Permissive UR
tCoord
Set
= 0 ms
tSendMin
Set
= 0.1 s
Unblock
Disabled
Set
=
Set
tSecurity
= 0.035 s
Permissive overreaching scheme
Operation
Enabled
Set
=
Scheme type
Permissive OR
Set
=
tCoord
Set
= 0 ms
Set
tSendMin
= 0.1 s (0 s in parallel line applications)
Set
Unblock
=
Disabled
tSecurity
Set
= 0.035 s
Unblocking scheme
Unblock
Restart
Set
=
(Loss of guard signal will give both trip and alarm
Choose
tSecurity
Set
= 0.035 s
NoRestart if Unblocking scheme with no alarm for loss of guard is to be
Restart if Unblocking scheme with alarm for loss of guard is to be used)
NoRestart if only trip is required)
Section 16
Scheme communication
755