Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

1MRK 506 369-UUS -
Line distance protection REL670 2.2 ANSI
Application manual
It usually takes a bit of a time before the spark gap flashes, and sometimes the fault current
will be of such a magnitude that there will not be any flashover and the negative
impedance will be sustained. If equation
<
<
+
X
X
X
X
11
C
S
11
EQUATION1898 V1 EN
in figure 97, the fault current will have the same direction as when the capacitor is
bypassed. So, the directional measurement is correct but the impedance measured is
negative and if the characteristic crosses the origin shown in figure
operate. However, if there is a memory circuit designed so it covers the negative
impedance, a three phase fault can be successfully cleared by the distance protection. As
soon as the spark gap has flashed the situation for protection will be as for an ordinary
fault. However, a good protection system should be able to operate correctly before and
after gap flashing occurs.
jX
X
12
X
11
Z
S
X
C
en06000625.vsd
IEC06000625 V1 EN
Figure 215:
Cross-polarized
quadrilateral
characteristic
If the distance protection is equipped with a ground-fault measuring unit, the negative
impedance occurs when
×
>
×
+
3
X
2
X
X
C
1 _ 11
0 _ 11
EQUATION1919 V1 EN
Cross-polarized distance protection (either with mho or quadrilateral characteristic) will
normally handle ground-faults satisfactory if the negative impedance occurs inside the
characteristic. The operating area for negative impedance depends upon the magnitude of
72
is valid
jX
R
RV
R
Z
S
IEC06000584-SMALL V1 EN
Figure 216:
Section 8
Impedance protection
(Equation 376)
97
the IED cannot
X
12
X
11
R
R
FW
X
C
en06000584_small.vsd
Quadrilateral
characteristic with
separate impedance and
directional measurement
(Equation 377)
417