Proxy For Signals From Switching Device Via Goose Xlnproxy - ABB RELION 670 SERIES Applications Manual

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

Section 15
Control
15.3.3.4
15.3.3.5
698
tClosePulse is the output pulse length for a close command. If AdaptivePulse is set to
Adaptive, it is the maximum length of the output pulse for an open command. The default
length is set to 200 ms for a circuit breaker (SXCBR) and 500 ms for a disconnector
(SXSWI).

Proxy for signals from switching device via GOOSE XLNPROXY

The SwitchType setting controls the evaluation of the operating capability. If SwitchType
is set to Circuit Breaker, the input OPCAP is interpreted as a breaker operating capability,
otherwise it is interpreted as a switch operating capability.
Table 51:
Operating capability values for breaker/switches
Value
Breaker operating capability, CbOpCap
1
None
2
Open
3
Close – Open
4
Open – Close – Open
5
Close – Open – Close – Open
6
Open – Close – Open – Close – Open
7
more
tStartMove is the supervision time for the apparatus to start moving after a command
execution is done from the SCSWI function. When the time has expired, the command
supervision is reset, and a cause-code is given.
During the tIntermediate time, the position indication is allowed to be in an intermediate
(00) state. When the time has expired, the command supervision is reset, and a cause-code
is given. The indication of the mid-position at SCSWI is suppressed during this time
period when the position changes from open to close or vice-versa if the parameter
SuppressMidPos is set to On in the SCSWI function.
In most cases, the same value can be used for both tStartMove and tIntermediate as in the
source function. However, tStartMove may need to be increased to accommodate for the
communication delays, mainly when representing a circuit breaker.
Bay Reserve (QCRSV)
The timer tCancelRes defines the supervision time for canceling the reservation, when this
cannot be done by requesting bay due to for example communication failure.
When the parameter ParamRequestx (x=1-8) is set to Only own bay res. individually for
each apparatus (x) in the bay, only the own bay is reserved, that is, the output for
1MRK 506 369-UUS -
Switch operating capability, SwOpCap
None
Open
Close
Close and Open
Larger values handled as 4, both Close and Open
Line distance protection REL670 2.2 ANSI
Application manual