Zone Reach Setting Higher Than Minimum Load Impedance - ABB RELION 670 SERIES Applications Manual

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

1MRK 506 369-UUS -
8.13.4.9
Line distance protection REL670 2.2 ANSI
Application manual
é
£
×
×
RFPG
0.8
Z
ê
ë
load
min
GUID-11DD90FA-8FB5-425F-A46F-6553C00025BE V1 EN
Where:
ϑ
is a maximum load-impedance angle, related to the maximum load power.
To avoid load encroachment for the phase-to-phase measuring elements, the set resistive
reach of any distance protection zone must be less than 160% of the minimum load
impedance.
RFPPZx 
1.6 Z
load
EQUATION579 V3 EN
Equation
147
is applicable only when the loop characteristic angle for the phase-to-phase
faults is more than three times as large as the maximum expected load-impedance angle.
More accurate calculations are necessary according to equation 148.
 
RFPPZx 1.6 Z
load min
IECEQUATION2307 V2 EN
All this is applicable for all measuring zones when no Power swing detection function
ZMRPSB (78) is activated in the IED. Use an additional safety margin of approximately
20% in cases when a ZMRPSB (78) function is activated in the IED, refer to the
description of Power swing detection function ZMRPSB (78).

Zone reach setting higher than minimum load impedance

The impedance zones are enabled as soon as the (symmetrical) load impedance crosses the
vertical boundaries defined by RLdFwd and RldRev or the lines defined by ArgLd. So, it
is necessary to consider some margin. It is recommended to set RLdFwd and RldRev to
90% of the per-phase resistance that corresponds to maximum load.
The absolute value of the margin to the closest LdAngle line should be of the same order,
that is, at least 0.1 • Z
load min
The load encroachment settings are related to a per-phase load impedance in a
symmetrical star-coupled representation. For symmetrical load or three-phase and phase-
to-phase faults, this corresponds to the per-phase, or positive-sequence, impedance. For a
×
+
2
R
1
R
0
¶ -
×
cos
sin
×
+
2
X
1
X
0
R1Zx
cos
sin
X1Zx
.
Impedance protection
ù
ú
û
Section 8
(Equation 397)
(Equation 398)
(Equation 399)
431

Advertisement

Table of Contents
loading

Table of Contents