Application manual
tPCrvx, tACrvx, tBCrvx, tCCrvx: Parameters for programmable inverse time
characteristic curve. The time characteristic equation is according to equation 460:
æ
ç
A
ç
[ ]
=
t s
ç
p
æ
ö
i
ç
-
C
ç
÷
è
è
ipickup
ø
EQUATION1722 V1 EN
Further description can be found in the Technical reference manual (TRM).
tPRCrvx, tTRCrvx, tCRCrvx: Parameters for customer creation of inverse reset time
characteristic curve. Further description can be found in the Technical Reference Manual.

Common settings for all steps

x means step 1, 2, 3 and 4.
AngleRCA: Relay characteristic angle given in degrees. This angle is defined as shown in
figure 263. The angle is defined positive when the residual current lags the reference
voltage (Vpol = -)
ö
÷
÷
+
×
B
TD
÷
÷
ø
Section 9
Current protection
(Equation 467)