ABB RELION 670 SERIES Applications Manual page 913

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

1MRK 506 369-UUS -
Line distance protection REL670 2.2 ANSI
Application manual
Example 2
SMAI1:13
BLOCK
SPFCOUT
DFTSPFC
AI3P
^GRP1_A
AI1
^GRP1_B
AI2
^GRP1_C
AI3
^GRP1_N
AI4
TYPE
AIN
ANSI07000199 V1 EN
Figure 418:
Configuration for using an instance in task time group 2 as DFT
reference.
Assume instance SMAI4:16 in task time group 2 has been selected in the configuration to
control the frequency tracking for all instances. Observe that the selected reference
instance (i.e. frequency tracking master) must be a voltage type. Observe that positive
sequence voltage is used for the frequency tracking feature.
For task time group 1 this gives the following settings (see Figure
SMAI1:1 – SMAI12:12: DFTReference = ExternalDFTRef to use DFTSPFC input as
reference (SMAI4:16)
For task time group 2 this gives the following settings:
SMAI1:13: DFTRefExtOut = DFTRefGrp4 to route SMAI4:16 reference to the
SPFCOUT output, DFTReference = DFTRefGrp4 for SMAI1:13 to use SMAI4:16 as
reference (see Figure 418) SMAI2:14 – SMAI12:24: DFTReference = DFTRefGrp4 to
use SMAI4:16 as reference.
For task time group 3 this gives the following settings:
SMAI1:25 – SMAI12:36: DFTReference = ExternalDFTRef to use DFTSPFC input as
reference (SMAI4:16)
Basic IED functions
SMAI1:1
BLOCK
SPFCOUT
DFTSPFC
AI3P
^GRP1_A
AI1
^GRP1_B
AI2
^GRP1_C
AI3
^GRP1_N
AI4
TYPE
AIN
SMAI1:25
BLOCK
SPFCOUT
DFTSPFC
AI3P
^GRP1_A
AI1
^GRP1_B
AI2
^GRP1_C
AI3
^GRP1_N
AI4
TYPE
AIN
ANSI07000198.vsd
416
Section 24
for numbering):
907