ABB RELION 670 SERIES Applications Manual page 449

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

1MRK 506 369-UUS -
Line distance protection REL670 2.2 ANSI
Application manual
Do not forget to adjust the setting of load encroachment resistance
RLdFwd in Phase selection with load encroachment (FDPSPDIS, 21 or
FRPSPDIS, 21) to the value equal to or less than the calculated value
RLdInFw. It is at the same time necessary to adjust the load angle in
FDPSPDIS (21) or FRPSPDIS (21) to follow the condition presented in
equation 418.
Index PHS designates correspondence to FDPSPDIS (21) or FRPSPDIS
(21) function and index PSD the correspondence to ZMRPSB (68)
function.
é
tan(
³
arctan
LdAngle
ê
PHS
ë
EQUATION1737-ANSI V1 EN
Consider equation 419,
=
°
j
25
=
LdAngle
max
PSD
EQUATION1739-ANSI V1 EN
then it is necessary to set the load angle in FDPSPDIS (21) or FRPSPDIS (21) function to
not less than equation 420.
é
tan(LdAngle
³
LdAngle
arctan
ê
PHS
ë
EQUATION1738-ANSI V1 EN
It is recommended to set the corresponding resistive reach parameters in reverse direction
(RLdOutRv and kLdRRv) to the same values as in forward direction, unless the system
operating conditions, which dictate motoring and generating types of oscillations,
requires different values. This decision must be made on basis of possible system
contingency studies especially in cases, when the direction of transmitted power may
change fast in short periods of time. It is recommended to use different setting groups for
operating conditions, which are changing only between different periods of year (summer,
winter).
System studies should determine the settings for the hold timer tH. The purpose of this
timer is, to secure continuous output signal from Power swing detection function
(ZMRPSB, 68) during the power swing, even after the transient impedance leaves
ZMRPSB (68) operating characteristic and is expected to return within a certain time due
ù
LdAngle
)
PSD
ú
û
KLdRFw
ù
)
=
PSD
arctan
ú
û
kLdRFw
Section 8
Impedance protection
°
é
ù
tan(25 )
=
°
37.5
ê
ú
ë
û
0.61
(Equation 418)
(Equation 419)
(Equation 420)
443