ABB RELION 670 SERIES Applications Manual page 281

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

1MRK 506 369-UUS -
Line distance protection REL670 2.2 ANSI
Application manual
2
V
=
Zload
min
S
EQUATION1753-ANSI V1 EN
Where:
V
is the minimum phase-to-phase voltage in kV
S
is the maximum apparent power in MVA.
The load impedance [Ω/phase] is a function of the minimum operation voltage and the
maximum load current:
V
Zload =
min
×
3 I
max
EQUATION1754-ANSI V1 EN
Minimum voltage V
and maximum current I
min
conditions. Minimum load impedance occurs normally under emergency conditions.
To avoid load encroachment for the phase-to-ground measuring elements, the set
impedance reach of any distance protection zone must be less than 80% of the minimum
load impedance.
For setting of the ground-fault loop, the following formula can be used:
Z
LOAD
ZPG
1 6
.
(
cos β
2 1
EQUATION1604-ANSI V1 EN
where:
Z
= magnitude of minimum load impedance
load
ZPG
= 180°-2·g =180°–2(ArgPG-Q
The formula is derived by trigonometric analyze of the figure 134. The length of the vector
from the origin O to the point F on the circle is defined by the law of cosine. The result
gives the maximum diameter (RFPE) for which the load impedance touch the circle with
the given load condition. Use an extra margin of 20% to give sufficient distance between
the calculated minimum load impedance and relay boundary.
max
)
( )
)
Load
Section 8
Impedance protection
are related to the same operating
(Equation 183)
(Equation 184)
(Equation 185)
275