Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

1MRK 506 369-UUS -
Line distance protection REL670 2.2 ANSI
Application manual
They must generally be blocked during normal operation and released during power
swings.
Their operation must be time delayed but shorter (with sufficient margin) than the set
time delay of normal distance protection zone 2, which is generally blocked by the
power swing.
Their resistive reach setting must secure, together with the set time delay for their
operation, that the slowest expected swings pass the impedance operate area without
initiating their operation.
Communication and tripping logic as used by the power swing distance protection zones
is schematically presented in figure 230.
The operation of the power swing zones is conditioned by the operation of Power swing
detection (ZMRPSB, 68) function. They operate in PUTT or POTT communication
scheme with corresponding distance protection zones at the remote line end. It is preferred
to use the communication channels over the optionally available "Line Data
Communication Module - LDCM" and the "Binary signal transfer to remote end"
function. It is also possible to include, in an easy way (by means of configuration
possibilities), the complete functionality into regular scheme communication logic for the
distance protection function. The communication scheme for the regular distance
protection does not operate during the power-swing conditions, because the distance
protection zones included in the scheme are normally blocked. The powerswing zones can
for this reason use the same communication facilities during the power-swing conditions.
Only one power swing zone is necessary in distance protection at each line terminal, if the
POTT communication scheme is applied. One underreaching power swing zone, which
sends the time delayed carrier signal, and one overreaching power swing zone, which
performs the local tripping condition, are necessary with PUTT schemes.
The operation of the distance protection zones with long time delay (for example, zone 3)
is in many cases not blocked by the power swing detection elements. This allows in such
cases the distance protection zone 3 (together with the full-scheme design of the distance
protection function) to be used at the same time as the overreaching power-swing zone.