Example; Examples How To Connect, Configure And Set Vt Inputs For Most Commonly Used Vt Connections - ABB REB670 Applications Manual

Relion 670 series busbar protection
Hide thumbs Also See for REB670:
Table of Contents

Advertisement

1MRK 505 370-UUS A
4.2.4.1
4.2.4.2
Busbar protection REB670 2.2 ANSI
Application manual

Example

Consider a VT with the following data:
132kV
120V
3
3
EQUATION1937 V1 EN-US
The following setting should be used: VTprim=132 (value in kV) VTsec=120 (value in
V)
Examples how to connect, configure and set VT inputs for most
commonly used VT connections
Figure
27
defines the marking of voltage transformer terminals commonly used around
the world.
+
+
V
V
Pri
Sec
a)
ANSI11000175 V1 EN-US
Figure 27:
Commonly used markings of VT terminals
Where:
a)
is the symbol and terminal marking used in this document. Terminals marked with a square
indicate the primary and secondary winding terminals with the same (positive) polarity
b)
is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-
ground connected VTs
c)
is the equivalent symbol and terminal marking used by IEC (ANSI) standard for open delta
connected VTs
d)
is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-phase
connected VTs
It shall be noted that depending on national standard and utility practices the rated
secondary voltage of a VT has typically one of the following values:
a
A
A
(X1)
(H1)
(H1)
N
n
N
(H2)
(X2)
(H2)
b)
Section 4
Analog inputs
da
A
(X1)
(H1)
dn
B
(X2)
(H2)
c)
d)
ANSI11000175_1_en.vsd
SEMOD55055-47 v3
(Equation 1)
SEMOD55055-60 v6
a
(X1)
b
(X2)
85