ABB RELION 670 SERIES Applications Manual page 159

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

1MRK 506 369-UUS -
Line distance protection REL670 2.2 ANSI
Application manual
Phase-to-phase current variation
Zero sequence current criterion
Low voltage criterion
Low current criterion
Phase-to-phase current variation takes the current samples (IL1–IL2, IL2–IL3, etc.) as
input and it calculates the variation using the sampling value based algorithm. Phase-to-
phase current variation function is major one to fulfil the objectives of the start up element.
Zero sequence criterion takes the zero sequence current as input. It increases security of
protection during the high impedance fault conditions.
Low voltage criterion takes the phase voltages and phase to phase voltages as inputs. It
increases the security of protection when the three phase fault occurred on the weak end
side.
Low current criterion takes the phase currents as inputs and it increases the dependability
during the switch onto fault case of unloaded line.
The differential function can be allowed to trip as no load is fed through the line and
protection is not working correctly.
Features:
Startup element is sensitive enough to detect the abnormal status of the protected
system
Startup element does not influence the operation speed of main protection
Startup element detects the evolving faults, high impedance faults and three phase
fault on weak side
It is possible to block the each sub function of startup element
Startup signal has a settable pulse time
The Additional security logic for differential protection LDRGFC (11) is connected as a
local criterion to release the tripping from line differential protection. LDRGFC is
connected with an AND gate to the trip signals from LDLPDIF function. Figure
a configuration for three phase tripping, but LDRGFC can be configured with individual
release to all phases trip. The BFI_3P signal can also, through one of the available binary
signal transfer channels, be sent to remote end and there connected to input REMSTEP.
Normally, the local criterion is sufficient.
Section 7
Differential protection
56
shows
153