Application - ABB RELION 670 SERIES Applications Manual

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

1MRK 506 369-UUS -
16.8.8.2
16.8.8.3
16.8.9
Line distance protection REL670 2.2 ANSI
Application manual

Application

Zero sequence symmetrical components are present in all abnormal conditions involving
ground. They have a considerably high value during ground faults.
Zero sequence overvoltage protection (LCZSPTOV, 59N) is a definite time stage
comparator function. The Zero sequence input voltage from the SMAI block is connected
as input to the function through a group connection V3P in PCM600. This voltage is
compared against the preset value and a pickup signal will be set high if the input zero
sequence voltage is more than the preset value 3V0PU. Trip signal will be set high after
a time delay setting of t3V0. BLOCK input will block the complete function. BLKTR will
block the trip output . Zero sequence voltage will be available as service value output as
3V0.
Setting guidelines
GlobalBaseSel: Selects the global base value group used by the function to define IBase,
VBase and SBase as applicable.
The IED is fed from a normal voltage transformer group where the residual voltage is
created from the phase to ground voltages within the protection software or the residual
voltage is fed from a broken delta-connected VT-group. The setting of analogue inputs
always gives 3U0. Therefore set:
V
ph - ph
VBase=
3
EQUATION2268-ANSI V1 EN
3V0PU: Level of high zero sequence voltage detection given in % of VBase. This setting
should be based on fault calculations to find the zero sequence voltage in case of a fault at
the most remote point where the direct trip scheme shall be active. The zero sequence
voltages shall be calculated for different types of ground faults (single phase to ground and
phase to phase to ground short circuits) at different switching states in the network.
t3V0: Time delay for trip in case of high zero sequence voltage detection. The trip function
can be used as stand alone ground fault protection with a long time delay. The choice of
time delay is depending on the application of the protection as well as network topology.
Negative sequence overcurrent protection LCNSPTOC (46)
Section 16
Scheme communication
(Equation 535)
785

Advertisement

Table of Contents
loading

Table of Contents