Long Transmission Line Application - ABB RELION 670 SERIES Applications Manual

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

Section 8
Impedance protection
8.3.2.5
230
In short line applications, the major concern is to get sufficient fault resistance coverage.
Load encroachment is not so common. The line length that can be recognized as a short
line is not a fixed length; it depends on system parameters such as voltage and source
impedance, see table 19.
Table 19:
Definition of short and very short line
Line category
Vn
110 kV
Very short line
0.75 -3.5mile
Short line
4-7 miles
The IED's ability to set resistive and reactive reach independent for positive and zero
sequence fault loops and individual fault resistance settings for phase-to-phase and phase-
to-ground fault together with load encroachment algorithm improves the possibility to
detect high resistive faults without conflict with the load impedance, see figure 112.
For very short line applications, the underreaching zone 1 can not be used due to the
voltage drop distribution throughout the line will be too low causing risk for overreaching.
It is difficult, if not impossible, to apply distance protection for short lines. It is possible
to apply an overreaching pilot communication based POTT or Blocking scheme
protection for such lines to have fast tripping along the entire line. Usually a unit
protection, based on comparison of currents at the ends of the lines is applied for such
lines.
Load encroachment is normally no problem for short line applications.

Long transmission line application

For long transmission lines, the margin to the load impedance, that is, to avoid load
encroachment, will normally be a major concern. It is well known that it is difficult to
achieve high sensitivity for phase-to-ground fault at remote line end of long lines when the
line is heavy loaded.
What can be recognized as long lines with respect to the performance of distance
protection can generally be described as in table 20, long lines have Source impedance
ratio (SIR's) less than 0.5.
Table 20:
Definition of long and very long lines
Line category
Vn
110 kV
Long lines
45-60 miles
Very long lines
>60 miles
Vn
500 kV
3-15 miles
15-30 miles
Vn
500 kV
200-250 miles
>250 miles
Line distance protection REL670 2.2 ANSI
1MRK 506 369-UUS -
Application manual