Single Circuit Breaker With Single Busbar - ABB RELION 670 SERIES Applications Manual

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

1MRK 506 369-UUS -
15.1.3.1
Line distance protection REL670 2.2 ANSI
Application manual

Single circuit breaker with single busbar

Fuse
VT
1Voltage
bus
V
REF
1
lineVoltage/1/2/3
VA/VB/VC
ANSI10000093 V1 EN
Figure 302:
Connection of SESRSYN (25) function block in a single busbar
arrangement
Figure
302
illustrates connection principles for a single busbar. For the SESRSYN (25)
function there is one voltage transformer on each side of the circuit breaker. The voltage
transformer circuit connections are straightforward; no special voltage selection is
necessary.
The voltage from busbar VT is connected to V3PB1 and the voltage from the line VT is
connected to V3PL1. The conditions of the VT fuses shall also be connected as shown
above. The voltage selection parameter CBConfig is set to No voltage sel.
Bus 1
189
152
Fuse
VT
Line
Section 15
Control
SESRSYN (25)
V3PB1*
SYNOK
V3PB2*
AUTOSYOK
V3PL1*
AUTOENOK
V3PL2*
MANSYOK
BLOCK
MANENOK
BLKSYNCH
TSTSYNOK
BLKSC
TSTAUTSY
BLKENERG
TSTMANSY
BUS1_OP
TSTENOK
BUS1_CL
VSELFAIL
BUS2_OP
B1SEL
BUS2_CL
B2SEL
LINE1_OP
L1SEL
LINE1_CL
L2SEL
LINE2_OP
SYNPROGR
LINE2_CL
SYNFAIL
VB1OK
VOKSYN
VB1FF
VDIFFSYN
VB2OK
FRDIFSYN
VB2FF
FRDIFFOK
VL1OK
FRDERIVA
VL1FF
VOKSC
VL2OK
VDIFFSC
VL2FF
FRDIFFA
STARTSYN
PHDIFFA
TSTSYNCH
FRDIFFM
TSTSC
PHDIFFM
TSTENERG
INADVCLS
AENMODE
VDIFFME
MENMODE
FRDIFFME
PHDIFFME
Vbus
VLine
MODEAEN
MODEMEN
ANSI0000093-1-en.vsd