Settings - ABB RELION 670 SERIES Applications Manual

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

1MRK 506 369-UUS -
10.4.3.2
Line distance protection REL670 2.2 ANSI
Application manual
BLOCK: The input will block the operation of the Overexcitation protection OEXPVPH
(24), for example, the block input can be used to block the operation for a limited time
during special service conditions.
RESET: OEXPVPH (24) has a thermal memory, which can take a long time to reset.
Activation of the RESET input will reset the function instantaneously.
Recommendations for Output signals
Please see the default factory configuration for examples of configuration.
ERROR: The output indicates a measuring error. The reason, for example, can be
configuration problems where analogue signals are missing.
BFI: The BFI output indicates that the level Pickup1> has been reached. It can be used to
initiate time measurement.
TRIP: The TRIP output is activated after the operate time for the V/f level has expired.
TRIP signal is used to trip the circuit breaker(s).
ALARM: The output is activated when the alarm level has been reached and the alarm
timer has elapsed. When the system voltage is high this output sends an alarm to the
operator.

Settings

GlobalBaseSel: Selects the global base value group used by the function to define IBase,
VBase and SBase as applicable.
Operation: The operation of the Overexcitation protection OEXPVPH (24) can be set to
Enabled/Disabled.
MeasuredV: The phases involved in the measurement are set here. Normally the three
phase measurement measuring the positive sequence voltage should be used but when
only individual VT's are used a single phase-to-phase can be used.
MeasuredI: The phases involved in the measurement are set here. MeasuredI: must be in
accordance with MeasuredV.
Pickup1: Operating level for the inverse characteristic, IEEE or tailor made. The operation
is based on the relation between rated voltage and rated frequency and set as a percentage
factor. Normal setting is around 108-110% depending of the capability curve for the
transformer/generator.
Pickup2: Operating level for the t_MinTripDelay definite time delay used at high
overvoltages. The operation is based on the relation between rated voltage and rated
frequency and set as a percentage factor. Normal setting is around 110-180% depending
Section 10
Voltage protection
583