ABB RELION 670 SERIES Applications Manual page 559

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

1MRK 506 369-UUS -
Line distance protection REL670 2.2 ANSI
Application manual
Operate
Angle1(2) = 0
Power1(2)
IEC06000556 V1 EN
Figure 284:
For low forward power the set angle should be 0° in the underpower
function
TripDelay1(2) is set in seconds to give the time delay for trip of the stage after pick up.
Hysteresis1(2) is given in p.u. of generator rated power according to equation 495.
=
×
×
S
3 VBase IBase
N
EQUATION2047 V1 EN
The drop out power will be Power1(2) + Hysteresis1(2).
The possibility to have low pass filtering of the measured power can be made as shown in
the formula:
S TD S
(
1
TD S
)
=
+
Old
Calculated
EQUATION1893-ANSI V1 EN
Where
S
is a new measured value to be used for the protection function
S
is the measured value given from the function in previous execution cycle
old
S
is the new calculated value in the present execution cycle
Calculated
TD
is settable parameter
Q
°
en06000556.vsd
Section 9
Current protection
P
(Equation 495)
(Equation 496)
553