Setting Of Zones For Parallel Line Application - ABB RELION 670 SERIES Applications Manual

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

Section 8
Impedance protection
8.3.3.5
244

Setting of zones for parallel line application

Parallel line in service – Setting of zone 1
With reference to section
the protected line.
However, influence of mutual impedance has to be taken into account.
Parallel line in service – setting of zone 2
Overreaching zones (in general, zones 2 and 3) must overreach the protected circuit in all
cases. The greatest reduction of a reach occurs in cases when both parallel circuits are in
service with a single phase-to-ground fault located at the end of a protected line. The
equivalent zero sequence impedance circuit for this case is equal to the one in figure
in section
"Parallel line in
The components of the zero sequence impedance for the overreaching zones must be equal
to at least:
R
=
R
+
R
0E
0
m0
EQUATION553 V1 EN
X
X
X
=
+
0E
0
m0
EQUATION554 V1 EN
Check the reduction of a reach for the overreaching zones due to the effect of the zero
sequence mutual coupling. The reach is reduced for a factor:
Z
0
m
= -
K
0 1
×
+
+
2
Z
1
Z
0
R
f
EQUATION1426 V1 EN
If the denominator in equation
and imaginary part of the reach reduction factor for the overreaching zones can be written
as:
( )
×
X m
0
Re
( )
= -
Re
K
0
1
( )
2
+
Re
B
Im
EQUATION1427 V2 EN
"Parallel line
applications", the zone reach can be set to 85% of
service".
134
is called B and Z0m is simplified to X0m, then the real
B
( )
2
B
1MRK 506 369-UUS -
(Equation 132)
(Equation 133)
(Equation 134)
(Equation 135)
Line distance protection REL670 2.2 ANSI
Application manual
115

Advertisement

Table of Contents
loading

Table of Contents