Command
Open the genset breaker
Acknowledge alarms
4.4

Test mode

Push the Mode selection
input.
In test mode, the genset breaker only closes if you push the Genset breaker
mode, the test mode timer starts. After the Stop/Config
a stop command to the genset. The genset stops as specified by the stop sequence.
More information
See Stop sequence for an overview of what happens during the stop sequence.
4.5

Deep sleep

You can use the deep sleep function to extend the battery life. This function allows you to stop all standard functions on the
controller and lower the power consumption. The controller keeps the same status and alarms as before it went into deep
sleep mode. Standard functions are activated when the controller is no longer in deep sleep mode.
In the smart connect software or on the controller, go to Module > General > Deep Sleep Mode to enable the deep
sleep function. The controller goes into deep sleep mode after an adjustable time of inactivity. You can configure this timer
in Timers > General > Deep Sleep Mode Delay. Push a button to exit deep sleep mode.
Parameter
Deep Sleep Mode
Deep Sleep Mode Delay
The controller does not go into deep sleep mode if:
• The controller is in AUTO mode.
• Mains monitoring is enabled and the mains breaker is configured as an output.
• Modbus communication is enabled.
User manual 4189341341B EN
Description
The controller ramps down and opens the generator breaker at the breaker open point if
the mains breaker is closed. The controller opens the generator breaker instantly if the
mains breaker is open or the controller is in island mode.
Push the acknowledge button to acknowledge an alarm in manual and AUTO mode.
button until TEST is shown on the display. You can also activate the test mode with a digital
Range
Enable
Disable
5 to 1800s
button. Once the genset starts in test
button is pressed or the timer has expired, the controller sends
Default
Not enabled
10 s
Page 58 of 89