Parameter List - Deif CGC 200 Operator's Manual

Compact genset controller
Table of Contents

Advertisement

CGC 200 Operator's manual 4189340770
UK

4.1.2 Parameter list

The parameters used by CGC 200 that can be changed from the controller front panel are listed in the table
below.
Param-
Parameter
eter
name
num-
ber
P00
Auto start delay
P01
Auto stop delay
P02
Start attempts
P03
Start prepare
P04
Start on time
P05
Start off time
P06
Initial inhibit de-
lay
P07
Idle start
P08
GB close delay
P09
Cooldown time
P10
Idle stop
P11
Extended stop
P12
Stop failure
P13
Number of teeth
P14
Number of gen.
poles
P15
Hz/V OK delay
P16
G U >
P17
G U <
P18
G RPM <
DEIF A/S
Range
De-
fault
value
0 to 3600 s
1
0 to 3600 s
1
1 to 10
3
0 to 300 s
0
3 to 60 s
8
3 to 60 s
10
1 to 60 s
10
0 to 3600 s
0
3 to 3600 s
10
3 to 3600 s
10
0 to 3600 s
0
0 to 120 s
20
0 to 120 s
0
10 to 300
118
2 to 32
4
0 to 20.0 s
10.0
30 to 360 V
264
30 to 360 V
196
0 to 6000
1200
RPM
Value
Description
chos-
en*
Timer for starting using the Auto start
signal
Timer for stopping after the Auto start
signal is removed
Number of start attempts in one start se-
quence
Timer for start prepare
Timer for starter ON time during crank-
ing
Timer for starter OFF time before a new
start attempt is made
Timer for bypassing frequency and volt-
age shutdown during starting
Timer for idle speed after starting
Timer for generator breaker close after
frequency and voltage OK
Cooling down time
Timer for idle speed before stopping
Timer for extended stop
Maximum allowable time for stopping
the genset
The number of teeth on flywheel. This is
only used when MPU is selected as run-
ning detection (see P40).
The number of genset poles. This is
used in the frequency calculation.
Voltage and frequency OK delay after
starting of genset
Generator over-voltage protection
Generator under-voltage protection
Generator under-speed protection, if
running detection (see P40) is RPM in-
put only
Parameters