Installing and Configuring the Core Switch 2/64
Note:
source.
38
Ensure that two dedicated electrical branch circuits with the following
characteristics are available for use:
— 200 to 240 VAC, 50 - 60 Hertz.
— Protected by a circuit breaker in accordance with local electrical codes.
— Supply circuit, line fusing, and wire size that are adequate according to
the electrical rating on the chassis nameplate.
— Grounded outlets installed by a licensed electrician and compatible with
the power cords.
— Located close to the 14U HP StorageWorks Core Switch 2/64 chassis and
easily accessible.
To maximize fault tolerance, connect each power cord to a separate power
Ensure the HP StorageWorks Core Switch 2/64 has access to a minimum
airflow of 350 cubic feet per minute.
Ensure the air temperature measured at the blower inlet does not exceed 40
degrees Celsius during operation.
Core Switch 2/64 V4.1 Installation Guide