Figure 4-11 Cable Construction Influencing The Capacitance; Figure 4-12 Preferred Chain Connection For Multiple Motors; Table 4-9 Maximum Motor Cable Lengths (690V Drives) - Emerson unidrive sp User Manual

Universal variable speed ac drive for induction and servo motors model sizes 0 to 6
Hide thumbs Also See for unidrive sp:
Table of Contents

Advertisement

Safety
Product
Mechanical
Information
Information
Installation

Table 4-9 Maximum motor cable lengths (690V drives)

690V Nominal AC supply voltage
Maximum permissible motor cable length for each of
the following frequencies
Model
3kHz
4kHz
SP4601
SP4602
SP4603
SP4604
SP4605
250m
185m
(820ft)
(607ft)
SP4606
SP5601
SP5602
SP6601
SP6602
Cable lengths in excess of the specified values may be used only
when special techniques are adopted; refer to the supplier of the
drive.
The default switching frequency is 3kHz for open-loop and closed-
loop vector and 6kHz for servo.
4.8.2
High-capacitance cables
The maximum cable length is reduced from that shown in Table 4-6,
Table 4-7, Table 4-8 and Table 4-9 if high capacitance motor cables are
used.
Most cables have an insulating jacket between the cores and the armor
or shield; these cables have a low capacitance and are recommended.
Cables that do not have an insulating jacket tend to have high
capacitance; if a cable of this type is used, the maximum cable length is
half that quoted in the tables. (Figure 4-11 shows how to identify the two
types.)

Figure 4-11 Cable construction influencing the capacitance

Normal capacitance
Shield or armour
separated from the cores
The cable used for Table 4-6, Table 4-7, Table 4-8 and Table 4-9 is
shielded and contains four cores. Typical capacitance for this type of
cable is 130pF/m (i.e. from one core to all others and the shield
connected together).
4.8.3
Motor winding voltage
The PWM output voltage can adversely affect the inter-turn insulation in
the motor. This is because of the high rate of change of voltage, in
conjunction with the impedance of the motor cable and the distributed
nature of the motor winding.
For normal operation with AC supplies up to 500Vac and a standard
motor with a good quality insulation system, there is no need for any
special precautions. In case of doubt the motor supplier should be
consulted.
Special precautions are recommended under the following conditions,
but only if the motor cable length exceeds 10m:
AC supply voltage exceeds 500V
DC supply voltage exceeds 670V
Operation of 400V drive with continuous or very frequent sustained
braking
Multiple motors connected to a single drive
Unidrive SP User Guide
Issue Number: 13
Electrical
Getting
Basic
installation
Started
parameters
6kHz
8kHz
12kHz
90m
(295ft)
125m
(410ft)
High capacitance
Shield or armour close
to the cores
www.controltechniques.com
Running
SMARTCARD
Optimization
the motor
operation
For multiple motors, the precautions given in section 4.8.4 Multiple
motors should be followed.
For the other cases listed, it is recommended that an inverter-rated
motor be used. This has a reinforced insulation system intended by the
manufacturer for repetitive fast-rising pulsed voltage operation.
16kHz
Users of 575V NEMA rated motors should note that the specification for
inverter-rated motors given in NEMA MG1 section 31 is sufficient for
motoring operation but not where the motor spends significant periods
braking. In that case an insulation peak voltage rating of 2.2kV is
recommended.
If it is not practical to use an inverter-rated motor, an output choke
(inductor) should be used. The recommended type is a simple iron-cored
component with a reactance of about 2%. The exact value is not critical.
This operates in conjunction with the capacitance of the motor cable to
increase the rise-time of the motor terminal voltage and prevent
excessive electrical stress.
4.8.4
Multiple motors
Open-loop only
If the drive is to control more than one motor, one of the fixed V/F modes
should be selected (Pr 5.14 = Fd or SrE). Make the motor connections
as shown in Figure 4-12 and Figure 4-13. The maximum cable lengths in
Table 4-6, Table 4-7, Table 4-8 and Table 4-9 apply to the sum of the
total cable lengths from the drive to each motor.
It is recommended that each motor is connected through a protection relay
since the drive cannot protect each motor individually. For
sinusoidal filter or an output inductor must be connected as shown in
Figure 4-13, even when the cable lengths are less than the maximum
permissible. For details of inductor sizes refer to the supplier of the drive.

Figure 4-12 Preferred chain connection for multiple motors

Onboard
Advanced
Technical
Diagnostics
PLC
parameters
Data
Motor protection
relay
Chain connection (preferred)
UL Listing
Information
connection, a
77

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents