Getting Started; Onboard Plc Parameters; Figure 10-2 Programming Options For Unidrive Sp - Emerson unidrive sp User Manual

Universal variable speed ac drive for induction and servo motors model sizes 0 to 6
Hide thumbs Also See for unidrive sp:
Table of Contents

Advertisement

Safety
Product
Mechanical
Information
Information
Installation
The Onboard PLC and SYPTLite form the first level of functionality in a
range of programmable options for Unidrive SP.

Figure 10-2 Programming options for Unidrive SP

Level 1
Onboard PLC with SYPTLite software
SYPTLite can be used with either the Onboard PLC in the Unidrive SP
or with SM-Applications Lite to create ladder logic programs.
SYPT can be used with any of the Applications Modules to create fully
flexible programs using ladder logic, function blocks or DPL script.
10.4

Getting started

SYPTLite can be found on the CD which is supplied with the drive.
SYPTLite system requirements
Windows 2000/XP/Vista. Windows 95/98/98SE/Me/NT4 are not
supported
Pentium III 500MHz or better recommended
128MB RAM
Minimum of 800x600 screen resolution. 1024x768 is recommended
Adobe Acrobat 5.10 or later (for viewing User Guides)
Microsoft Internet Explorer V5.0 or later
RS232 to RS485, RJ45 communications lead to connect the PC to
the drive
Administrator rights are required to install the software
To install SYPTLite, insert the CD and the auto-run facility should start
up the front-end screen, from which SYPTLite can be selected.
See the SYPTLite help file for more information regarding using
SYPTLite, creating ladder diagrams and the available function blocks.
158
Electrical
Getting
Basic
installation
Started
parameters
www.controltechniques.com
Running
SMARTCARD
Optimization
the motor
operation
Level 2
SM-Applications Lite with
SYPTLite software
10.5

Onboard PLC parameters

The following parameters are associated with the Onboard PLC
program.
11.47
Drive Onboard PLC program enable
RW
Uni
0 to 2
This parameter is used to start and stop the drive Onboard PLC program.
Value
0
Halt the drive Onboard PLC program.
Run the drive Onboard PLC program (if installed). Any out-of-
range parameter writes attempted will be clipped to the
1
maximum / minimum values valid for that parameter before
being written.
Run the drive Onboard PLC program (if installed). Any out-of-
2
range parameter writes attempted will cause a 'UP ovr' trip.
11.48
Drive Onboard PLC program status
RO
Bi
-128 to +127
The drive Onboard PLC program status parameter indicates to the user
the actual state of the drive Onboard PLC program.
Onboard
Advanced
Technical
PLC
parameters
Data
Level 3
SM-Applications Lite with
SYPT software
CAPABILITY
Description
NC
Unidrive SP User Guide
UL Listing
Diagnostics
Information
Level 4
SM-Applications or
SM-Applications
Plus with SYPT
software
US
2
PT
Issue Number: 13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents