The trips can be grouped into the following categories. It should be noted that a trip can only occur when the drive is not tripped or is already tripped
but with a trip with a lower priority number.

Table 13-3 Trip categories

Priority
Category
1
Hardware faults
2
Non-resetable trips
3
EEF trip
4
SMARTCARD trips
Encoder power supply
4
trips
5
Autotune
Normal trips with
5
extended reset
5
Normal trips
5
Non-important trips
5
Phase loss
Drive over-heat based
5
on thermal model
6
Self-resetting trips
Although the UV trip operates in a similar way to all other trips, all drive
functions can still operate but the drive cannot be enabled. The following
differences apply to the UV trip:
1. Power-down save user parameters are saved when UV trip is
activated except when the main high voltage supply is not active
(i.e. operating in Low Voltage DC Supply Mode, Pr 6.44 = 1).
2. The UV trip is self-resetting when the DC bus voltage rises above
the drive restart voltage level. If another trip is active instead of UV at
this point, the trip is not reset.
3. The drive can change between using the main high voltage supply
and low voltage DC supply only when the drive is in the under
voltage condition (Pr 10.16 = 1). The UV trip can only be seen as
active if another trip is not active in the under voltage condition.
4. When the drive is first powered up a UV trip is initiated if the supply
voltage is below the restart voltage level and another trip is not
active. This does not cause save power down save parameters to be
saved at this point.
298
Electrical
Getting
Basic
installation
Started
parameters
Trips
These indicate serious internal problems and cannot be reset. The drive is inactive after
HF01 to HF16
one of these trips and the display shows HFxx. The Drive OK relay opens and the serial
comms will not function.
HF17 to HF32, SL1.HF,
Cannot be reset. Requires the drive to be powered down.
SL2.HF, SL3.HF
EEF
Cannot be reset unless a code to load defaults is first entered in Pr xx.00 or Pr 11.43.
C.boot, C.Busy, C.Chg,
C.OPtn, C.RdO, C.Err,
Can be reset after 1.0s
C.dat, C.FULL, C.Acc,
SMARTCARD trips have priority 5 during power-up
C.rtg, C.TyP, C.cpr,
C.Prod
Can be reset after 1.0s
PS.24V, EnC1
These trips can only override the following priority 5 trips: EnC2 to EnC8 or Enc11 to
Enc17
Can be reset after 1.0s, but the drive cannot be made to run unless it is disabled via the
tunE, tunE1 to tunE7
SAFE TORQUE OFF input (terminal 31), Drive enable (Pr 6.15) or the Control word
(Pr 6.42 and Pr 6.43).
OI.AC, OI.Br, OIAC.P,
Can be reset after 10.0s
OIBr.P, OIdC.P
All other trips not
Can be reset after 1.0s
included in this table
th, thS, Old1, cL2, cL3,
If Pr 10.37 is 1 or 3 (i.e. bit 0 set to 1), the drive will stop before tripping
SCL
PH
The drive attempts to stop before tripping
The drive attempts to stop before tripping, but if it does not stop within 10s the drive will
O.ht3
automatically trip
Under voltage trip cannot be reset by the user, but is automatically reset by the drive
UV
when the supply voltage is with specification
www.controltechniques.com
Running
SMARTCARD
Optimization
the motor
operation
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
Data
Comments
Unidrive SP User Guide
Issue Number: 13
UL Listing
Information

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents