Power stage thermistor 2 fault, or internal fan fault (size 3)
228
Hardware fault - return drive to supplier
HF29
Control board thermistor fault
229
Hardware fault - return drive to supplier
HF30
DCCT wire break trip from power module
230
Hardware fault - return drive to supplier
HF31
Internal capacitor bank fan failure (size 4 and larger) or a module has not powered up in a multi-module parallel drive
Check the AC or DC power supply to all modules in a multi-module parallel drive
231
If the AC or DC power supply is present, or if this is a single drive, then there is a hardware fault - return drive to the supplier
HF32
Power stage - Identification and trip information serial code error
232
Hardware fault - return drive to the supplier
It.AC
Output current overload timed out (I
Ensure the load is not jammed / sticking
Check the load on the motor has not changed
If seen during an autotune in servo mode, ensure that the motor rated current Pr 0.46 (Pr 5.07) or Pr 21.07 is ≤Heavy Duty current
rating of the drive
20
Tune the rated speed parameter (closed loop vector only)
Check feedback device signal for noise
Check the feedback device mechanical coupling
Ensure that the motor rated current is not set to zero
It.br
Braking resistor overload timed out (I
Ensure the values entered in Pr 10.30 and Pr 10.31 are correct
Increase the power rating of the braking resistor and change Pr 10.30 and Pr 10.31
19
If an external thermal protection device is being used and the braking resistor software overload is not required, set Pr 10.30 or
Pr 10.31 to 0 to disable the trip
L.SYnC
Drive failed to synchronize to the supply voltage in Regen mode
39
Refer to the Diagnostics chapter in the Unidrive SP Regen Installation Guide.
O.CtL
Drive control board over temperature
Check enclosure / drive fans are still functioning correctly
Check enclosure ventilation paths
23
Check enclosure door filters
Check ambient temperature
Reduce drive switching frequency
O.ht1
Power device over temperature based on thermal model
Reduce drive switching frequency
Reduce duty cycle
21
Decrease acceleration / deceleration rates
Reduce motor load
O.ht2
Heatsink over temperature
Check enclosure / drive fans are still functioning correctly
Check enclosure ventilation paths
Check enclosure door filters
Increase ventilation
22
Decrease acceleration / deceleration rates
Reduce drive switching frequency
Reduce duty cycle
Reduce motor load
Oht2.P
Power module heatsink over temperature
Check enclosure / drive fans are still functioning correctly
Check enclosure ventilation paths
Check enclosure door filters
Increase ventilation
105
Decrease acceleration / deceleration rates
Reduce drive switching frequency
Reduce duty cycle
Reduce motor load
288
Electrical
Getting
Basic
installation
Started
parameters
2
t) - accumulator value can be seen in Pr 4.19
2
t) – accumulator value can be seen in Pr 10.39
www.controltechniques.com
Running
SMARTCARD
Optimization
the motor
operation
Diagnosis
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
Data
Unidrive SP User Guide
Issue Number: 13
UL Listing
Information

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents