Incremental encoder with frequency and direction (F and D), or
Forward and Reverse (CW and CCW) signals, with or without commutation signals
Encoder type
Encoder power supply voltage
Encoder number of lines per
revolution
Encoder termination selection
Encoder error detection level
* These settings should only be used in closed loop vector mode, otherwise a phase offset test must be performed after every power up.
Absolute Sincos encoder with Hiperface or EnDat serial communications, or
Absolute EnDat communications only encoder
The Unidrive SP is compatible with the following Hiperface encoders:
SCS 60/70, SCM 60/70, SRS 50/60, SRM 50/60, SHS 170, LINCODER, SCS-KIT 101, SKS36, SKM36, SEK-53.
Encoder type
Encoder power supply voltage
Encoder auto configure enable
Encoder comms baud rate
(EndAt and SC.EndAt only)
Encoder error detection level
(SC.HiPEr and SC.EndAt only)
* See section 7.5.3 Restriction of encoder number of lines per revolution on page 135 for restrictions on this parameter.
134
Electrical
Getting
Basic
installation
Started
parameters
the motor
Fd (1) for frequency and direction signals without commutation signals *
Fr (2) for forward and reverse signals without commutation signals *
Pr 3.38
Fd.SErVO (4) for a frequency and direction encoder with commutation signals
Fr.SErVO (5) for forward and reverse signals with commutation signals
5V (0), 8V (1) or 15V (2)
Pr 3.36
NOTE
If output voltage from the encoder is >5V, then the termination resistors must be disabled Pr 3.39 to 0
Set to the number of pulses per revolution of the encoder divide by 2.
Pr 3.34
See section 7.5.3 Restriction of encoder number of lines per revolution on page 135 for restrictions
on this parameter.
0 = F or CW, D or CCW, Z termination resistors disabled
Pr 3.39
1 = F or CW, D or CCW termination resistors enabled and Z termination resistors disabled
2 = For CW, D or CCW, Z termination resistors enabled
0 = Error detection disable
1 = Wire break detection on F & D or CW & CCW, and Z inputs enabled
2 = Phase error detection (Fd.SErVO and Fr.SErVO only)
Pr 3.40
3 = Wire break detection on F & D or CW & CCW, and Z inputs and Phase error detection
(Fd.SErVO and Fr.SErVO only)
Termination resistors must be enabled for wire break detection to operate
SC.HiPEr (7) for a Sincos encoder with Hiperface serial communications
Pr 3.38
EndAt (8) for an EnDat communications only encoder
SC.EndAt (9) for a Sincos encoder with EnDat serial communications
Pr 3.36
5V (0), 8V (1) or 15V (2)
Setting this to 1 automatically sets up the following parameters:
Pr 3.33 Encoder turn bits
Pr 3.41
Pr 3.34 Encoder number of lines of revolution (SC.HiPEr and SC.EndAt only) *
Pr 3.35 Encoder single turn comms resolution
Alternatively these parameters can be entered manually.
Pr 3.37
100 = 100k, 200 = 200k, 300 = 300k, 500 = 500k, 1000 = 1M, 1500 = 1.5M, or 2000 = 2M
0 = Error detection disabled
1 = Wire break detection on Sin and Cos inputs
Pr 3.40
2 = Phase error detection
3 = Wire break detection on Sin and Cos inputs and phase error detection
www.controltechniques.com
Running
SMARTCARD
Optimization
operation
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
Data
Unidrive SP User Guide
Issue Number: 13