Figure 4-31 Sensitive Signal Circuit Clearance; Figure 4-32 Grounding The Drive, Motor Cable Shield And Filter; Figure 4-33 Grounding The Motor Cable Shield; Figure 4-34 Shielding Requirements Of Optional External Braking Resistor - Emerson unidrive sp User Manual

Universal variable speed ac drive for induction and servo motors model sizes 0 to 6
Hide thumbs Also See for unidrive sp:
Table of Contents

Advertisement

Safety
Product
Mechanical
Information
Information
Installation
Avoid placing sensitive signal circuits in a zone 300mm (12in) all around
the power module.

Figure 4-31 Sensitive signal circuit clearance

Ensure good EMC grounding.

Figure 4-32 Grounding the drive, motor cable shield and filter

Motor cable shield
(unbroken) electrically
connected to and held
in place by grounding
clamp.
88
Electrical
Getting
Basic
installation
Started
parameters
≥300mm
(12in)
Sensitive
signal
cable
Ensure direct
metal contact
at drive and
filter mounting
points (any
paint must be
removed).
www.controltechniques.com
Running
SMARTCARD
Optimization
the motor
operation
Connect the shield of the motor cable to the ground terminal of the motor
frame using a link that is as short as possible and not exceeding 50mm
(2in) long. A full 360
the motor is beneficial.
It is unimportant for EMC purposes whether the motor cable contains an
internal (safety) ground core, or there is a separate external ground
conductor, or grounding is through the shield alone. An internal ground
core will carry a high noise current and therefore it must be terminated
as close as possible to the shield termination.

Figure 4-33 Grounding the motor cable shield

Unshielded wiring to the optional braking resistor(s) may be used,
provided the wiring does not run external to the enclosure. Ensure a
minimum spacing of 300mm (12in) from signal wiring and the AC supply
wiring to the external EMC filter. Otherwise this wiring must be shielded.
Figure 4-34 Shielding requirements of optional external braking
resistor
Optional external
braking resistor
Enclosure
+DC
Onboard
Advanced
Technical
PLC
parameters
Data
°
termination of the shield to the terminal housing of
Optional external
braking resistor
Enclosure
BR
OR
Unidrive SP User Guide
UL Listing
Diagnostics
Information
+DC
BR
Issue Number: 13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents