0.15 {2.04}
Ramp mode select
RW
Txt
FASt (0)
OL
Std (1)
Std.hV (2)
FASt (0)
CL
Std (1)
Pr 0.15 sets the ramp mode of the drive as shown below:
0: Fast ramp
Fast ramp is used where the deceleration follows the programmed
deceleration rate subject to current limits. This mode must be used if a
braking resistor is connected to the drive.
1: Standard ramp
Standard ramp is used. During deceleration, if the voltage rises to the
standard ramp level (Pr 2.08) it causes a controller to operate, the output
of which changes the demanded load current in the motor. As the
controller regulates the link voltage, the motor deceleration increases as
the speed approaches zero speed. When the motor deceleration rate
reaches the programmed deceleration rate the controller ceases to
operate and the drive continues to decelerate at the programmed rate. If
the standard ramp voltage (Pr 2.08) is set lower than the nominal DC bus
level the drive will not decelerate the motor, but it will coast to rest. The
output of the ramp controller (when active) is a current demand that is fed
to the frequency changing current controller (Open-loop modes) or the
torque producing current controller (Closed-loop vector or Servo modes).
The gain of these controllers can be modified with Pr 4.13 and Pr 4.14.
Controller
operational
Motor Speed
Programmed
deceleration
rate
2: Standard ramp with motor voltage boost
This mode is the same as normal standard ramp mode except that the
motor voltage is boosted by 20%. This increases the losses in the motor,
dissipating some of the mechanical energy as heat giving faster
deceleration.
0.16 {8.39}
T28 and T29 auto-selection disable
RW
Bit
OL
OFF (0) or On (1)
Open-loop
When Pr 0.16 is set to 0, digital inputs T28 and T29 are set up
automatically with destinations according to the setting of the reference
select Pr 0.05.
Unidrive SP User Guide
Issue Number: 13
Electrical
Getting
Basic
installation
Started
parameters
the motor
US
Std (1)
DC Bus voltage
t
US
OFF (0)
www.controltechniques.com
Running
SMARTCARD
Optimization
operation
Reference select 0.05
Reference selection by
A1.A2 (0)
terminal input
Analog reference 1 or
A1.Pr (1)
presets selected by
terminal input
Analog reference 2 or
A2.Pr (2)
presets selected by
terminal input
Preset reference selected
Pr (3)
by terminal input
Keypad reference
PAd (4)
selected
Precision reference
Prc (5)
selected
Setting Pr 0.16 to 1 disables this automatic set-up, allowing the user to
define the function of digital inputs T28 and T29.
0.16 {2.02}
Ramp enable
RW
Bit
CL
OFF (0) or On (1)
Setting Pr 0.16 to 0 allows the user to disable the ramps. This is
generally used when the drive is required to closely follow a speed
reference which already contains acceleration and deceleration ramps.
0.17 {8.26}
T29 digital input destination
RW
Uni
OL
Pr 0.00 to Pr 21.51
Open-loop
Pr 0.17 sets the destination of digital input T29. This parameter is
normally set-up automatically according to the reference selected by
Pr 0.05. In order to manually set-up this parameter, the T28 and T29
auto-selection disable (Pr 0.16) must be set.
0.17 {4.12}
Current demand filter time constant
RW
Uni
CL
0.0 to 25.0 ms
Closed-loop
A first order filter, with a time constant defined by Pr 0.17, is provided on
the current demand to reduce acoustic noise and vibration produced as
a result of position feedback quantisation noise. The filter introduces a
lag in the speed loop, and so the speed loop gains may need to be
reduced to maintain stability as the filter time constant is increased.
0.18 {8.29}
Positive logic select
RW
Bit
OFF (0) or On (1)
Pr 0.18 sets the logic polarity for digital inputs and digital outputs. This
does not affect the drive enable input or the relay output.
0.19 {7.11}
Analog input 2 mode
RW
Txt
0 to 6
In modes 2 & 3 a current loop loss trip is generated if the current falls
below 3mA.
In modes 2 & 4 the analog input level goes to 0.0% if the input current
falls below 4mA.
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
Data
Terminal 28
function
Local / remote selector Jog select
Preset select bit 0
Preset select bit 0
Preset select bit 0
Local / remote selector Jog select
Local / remote selector Jog select
DE
VOLt (6)
UL Listing
Information
Terminal 29
function
Preset select bit 1
Preset select bit 1
Preset select bit 1
US
On (1)
PT
US
Pr 6.31
US
0.0
PT
US
On (1)
US
115