Optional External Emc Filters; Table 12-34 Size 6 (400V Only) Emission Compliance; Table 12-35 Size 6 (690V Only) Emission Compliance; Table 12-36 Emc Filter Cross Reference - Emerson unidrive sp User Manual

Universal variable speed ac drive for induction and servo motors model sizes 0 to 6
Hide thumbs Also See for unidrive sp:
Table of Contents

Advertisement

Safety
Product
Mechanical
Information
Information
Installation

Table 12-34 Size 6 (400V only) emission compliance

Motor cable length (m)
Using internal filter:
0 to 100
100 to max*
Using external filter:
0 to 100
*Refer to section 12.1.21 Maximum motor cable lengths on page 276.

Table 12-35 Size 6 (690V only) emission compliance

Motor cable length (m)
Using internal filter:
0 to 100
100 to max*
Using external filter:
0 to 25
0 to 100
*Refer to section 12.1.21 Maximum motor cable lengths on page 276.
Key (shown in decreasing order of permitted emission level):
E2R
EN 61800-3:2004 second environment, restricted distribution
(Additional measures may be required to prevent interference)
E2U
EN 61800-3:2004 second environment, unrestricted distribution
I
Industrial generic standard EN 50081-2 (EN 61000-6-4)
EN 61800-3:2004 first environment restricted distribution (The
following caution is required by EN 61800-3:2004)
This is a product of the restricted distribution class according
to IEC 61800-3. In a residential environment this product may
cause radio interference in which case the user may be
required to take adequate measures.
CAUTION
R
Residential generic standard EN 61000-6-3:2007
EN 61800-3:2004 first environment unrestricted distribution
EN 61800-3:2004 defines the following:
The first environment is one that includes residential premises. It
also includes establishments directly connected without intermediate
transformers to a low-voltage power supply network which supplies
buildings used for residential purposes.
The second environment is one that includes all establishments
other than those directly connected to a low-voltage power supply
network which supplies buildings used for residential purposes.
Restricted distribution is defined as a mode of sales distribution in
which the manufacturer restricts the supply of equipment to
suppliers, customers or users who separately or jointly have
technical competence in the EMC requirements of the application of
drives.
Unidrive SP User Guide
Issue Number: 13
Electrical
Getting
Basic
installation
Started
parameters
the motor
Switching frequency (kHz)
3
4
E2U
E2R
I
Switching frequency (kHz)
3
4
E2U
E2R
I
I
Do not use
www.controltechniques.com
Running
SMARTCARD
Optimization
operation
IEC 61800-3:2004 and EN 61800-3:2004
The 2004 revision of the standard uses different terminology to align the
requirements of the standard better with the EC EMC Directive.
6
Power drive systems are categorized C1 to C4:
Category
Intended for use in the first or second
C1
environments
Not a plug-in or movable device, and
intended for use in the first environment
C2
only when installed by a professional, or
in the second environment
6
Intended for use in the second
C3
environment, not the first environment
Rated at over 1000V or over 400A,
C4
intended for use in complex systems in
the second environment
Note that category 4 is more restrictive than E2R, since the rated current
of the PDS must exceed 400A or the supply voltage exceed 1000V, for
the complete PDS.
12.2

Optional external EMC filters

Table 12-36 EMC filter cross reference

Drive
SP0201 to SP0205 (1 phase)
SP0201 to SP0205 (3 phase)
SP1201 to SP1202
SP1203 to SP1204
SP2201 to SP2203
SP3201 to SP3202
SP4201 to SP4203
SP5201 to SP5202
SP0401 to SP0405
SP1401 to SP1404
SP1405 to SP1406
SP2401 to SP2404
SP3401 to SP3403
SP4401 to SP4403
SP5401 to SP5402
SP6401 to SP6402
SP3501 to SP3507
SP4601 to SP4606
SP5601 to SP5602
SP6601 to SP6602
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
Data
Definition
Schaffner
CT part no.
4200-6000
4200-6001
4200-6118
4200-6119
4200-6210
4200-6307
4200-6406
4200-6503
4200-6002
4200-6118
4200-6119
4200-6210
4200-6305
4200-6406
4200-6503
4200-6603
4200-6309
4200-6408
4200-6504
4200-6604
UL Listing
Information
Corresponding
code used
above
R
I
E2U
E2R
Epcos
CT part no.
4200-6121
4200-6120
4200-6211
4200-6306
4200-6405
4200-6501
4200-6121
4200-6120
4200-6211
4200-6306
4200-6405
4200-6501
4200-6601
4200-6308
4200-6407
4200-6502
4200-6602