Safety
Product
Mechanical
Information
Information
Installation
Pr
Pr
value
string
0
0-20
1
20-0
2
4-20.tr
4 - 20mA with trip on loss
3
20-4.tr
20 - 4mA with trip on loss
4
4-20
4 - 20mA with no trip on loss
5
20-4
20 – 4mA with no trip on loss
6
VOLt
Voltage mode
0.20 {7.14}
Analog input 2 destination
RW
Uni
DE
Pr 0.00 to Pr 21.51
Pr 0.20 sets the destination of analog input 2.
0.21 {7.15}
Analog input 3 mode
RW
Txt
0 to 9
Software V01.07.00 and later, the default is th (8)
Software V01.06.02 and earlier, the default is VOLt (6)
In modes 2 & 3 a current loop loss trip is generated if the current falls
below 3mA.
In modes 2 & 4 the analog input level goes to 0.0% if the input current
falls below 4mA.
Pr
Pr
value
string
0
0-20
1
20-0
2
4-20.tr
4 - 20mA with trip on loss
3
20-4.tr
20 - 4mA with trip on loss
4
4-20
4 - 20mA with no trip on loss
5
20-4
20 - 4mA with no trip on loss
6
VOLt
Voltage mode
Thermistor mode with short-
7
th.SC
circuit detection
Thermistor mode with no
8
th
short-circuit detection
Thermistor mode with
9
th.diSp
display only and no trip
0.22 {1.10}
Bipolar reference select
RW
Bit
OFF (0) or On (1)
Pr 0.22 determines whether the reference is uni-polar or bi-polar as
follows:
Pr 0.22
0
Unipolar speed/frequency reference
1
Bipolar speed/frequency reference
116
Electrical
Getting
Basic
installation
Started
parameters
Mode
Comments
0 - 20mA
20 - 0mA
Trip if I < 3mA
Trip if I < 3mA
0.0% if I ≤ 4mA
100% if I ≤ 4mA
PT
US
Pr 1.37
PT
US
th (8)
Mode
Comments
0 - 20mA
20 - 0mA
Trip if I < 3mA
Trip if I < 3mA
0.0% if I ≤ 4mA
100% if I ≤ 4mA
Th trip if R > 3K3
Th reset if R < 1K8
ThS trip if R < 50R
Th trip if R > 3K3
Th reset if R < 1K8
US
OFF (0)
Function
www.controltechniques.com
Running
SMARTCARD
Optimization
the motor
operation
0.23 {1.05}
Jog reference
RW
Uni
OL
0 to 400.0 Hz
CL
0 to 4,000.0 rpm
Enter the required value of jog frequency/speed.
The frequency/speed limits affect the drive when jogging as follows:
Frequency-limit parameter
Pr 0.01 Minimum reference clamp
Pr 0.02 Maximum reference clamp
0.24 {1.21}
Preset reference 1
RW
Bi
±Speed_limit_max rpm
0.25 {1.22}
Preset reference 2
RW
Bi
±Speed_limit_max rpm
0.26 {1.23}
Preset reference 3
RW
Bi
OL
±Speed_freq_max Hz/rpm
Open-loop
If the preset reference has been selected (see Pr 0.05), the speed at
which the motor runs is determined by these parameters.
0.26 {3.08}
Overspeed threshold
RW
Uni
CL
0 to 40,000 rpm
Closed-loop
If the speed feedback (Pr 3.02) exceeds this level in either direction, an
overspeed trip is produced. If this parameter is set to zero, the
overspeed threshold is automatically set to 120% x
SPEED_FREQ_MAX.
0.27 {1.24}
Preset reference 4
RW
Bi
OL
±Speed_freq_max Hz/rpm
Open-loop
Refer to Pr 0.24 to Pr 0.26.
0.27 {3.34}
Drive encoder lines per revolution
RW
Uni
VT
0 to 50,000
SV
Closed-loop
Enter in Pr 0.27 the number of lines per revolution of the drive encoder.
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
Data
Unidrive SP User Guide
Issue Number: 13
UL Listing
Information
US
0.0
Limit applies
No
Yes
US
0.0
US
0.0
US
0.0
US
0
US
0.0
US
1024