Station Number Setting - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

8.5.6

Station number setting

Set each station number so that no station number
overlaps.
The station number can be set without regard to the cable
connection order. There is no problem even if station
numbers are not consecutive.
Station
Station
No.3
No.7
GOT
Examples of station number setting
(1) Direct specification
When setting the device, specify the station number of
the temperature controller of which data is to be
changed.
Specification
range
1 to 99
(2) Indirect specification
When setting the device, indirectly specify the station
number of the inverter of which data is to be changed
using the 16-bit GOT internal data register (GD10 to
GD25).
When specifying the station No. from 100 to 115 on GT
Designer3, the value of GD10 to GD25 compatible to
the station No. specification will be the station No. of
the temperature controller.
Specification
Compatible
station NO.
device
100
GD10
101
GD11
102
GD12
103
GD13
104
GD14
105
GD15
106
GD16
107
GD17
108
GD18
109
GD19
110
GD20
111
GD21
112
GD22
113
GD23
114
GD24
115
GD25
8 - 32
8. CONNECTION TO YOKOGAWA TEMPERATURE CONTROLLER
8.5 Temperature Controller Side Setting
Station
Station
Station
No.1
No.15
No.6
Setting range
1 to 99
For the setting other than the above,
error (dedicated device is out of
range) will occur.
(3) All station specification
Target station differs depending on write-in operation or
read-out operation.
• For write-in operation, all station will be a target.In the
WORD BIT write-in operation, only the temperature
controller whose station No. is the same as host
address is applicable.
8.4.2 Communication detail settings
• In the read-out operation, only the temperature
controller whose station No. is the same as host
address is applicable.
For details of host address setting, refer to the
following.
8.4.2 Communication detail settings
POINT
POINT
POINT
The all station specification can be set for the following
temperature controllers only.
UT420, UT450, UT520, UT550, T551, UT750,
UP550, UP750,
US1000