(4) RS-485 connection diagram 4)
* 3
GOT side
RDA1
3
RDB1
4
SDA1
1
SDB1
2
SG
9
SDA2
5
SDB2
6
RDA2
7
RDB2
8
FG
10
*1
Pin No. of temperature controller differs depending on the model. Refer to the following table.
Signal name
SDB (+)
SDA (-)
RDB (+)
RDA (-)
SG
• For the product condition of UTAdvanced series, refer to the following table.
Model
UT55A
UP55A
*2
Terminating resistor should be provided for a temperature controller which will be a terminal.
*3
Set the terminating resistor of GOT side which will be a terminal.
■ Connecting terminating resistors
*4
Connect FG grounding to the appropriate part of a cable shield line.
Temperature controller
* 1
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
* 4
Terminating resistor(220Ω 1/4W)
GREEN
GREEN
Series
Series
UT32A/UP35A/UM33A
UT/UP/UM
US
Pin No.
Pin No.
Pin No.
23
21
301
24
22
302
25
23
304
26
24
305
27
25
303
Suffix code
Product
condition
Function
Open network
-
A
B
1 or 2
Other than 3
A
-
2
B
-
8. CONNECTION TO YOKOGAWA TEMPERATURE CONTROLLER
Temperature controller
* 4
* 2
Model of temperature controller
UTAdvanced Series
UT35A/
UT55A (product condition B)/
UT55A (product condition A)/
UP55A (product condition B)
UP55A (product condition A)
Pin No.
407
408
410
411
409
Optional suffix code
Product with the open network port of RS-
-
1
485 communication (4-wire type/2-wire
type)
Product with two RS-485 communication
-
Without "/LP"
ports (4-wire type/2-wire type) and without
the power supply for 24VDC sensor
Product without the additional contact
output points (DO) and with the open
-
1
network port of RS-485 communication (4-
wire type/2-wire type) (Standard code
model)
Product with the RS-485 communication
port (4-wire type/2-wire type) specified in
-
With "/CH3"
the E3 terminal area option (Detailed code
model)
Product with two RS-485 communication
-
-
ports (4-wire type/2-wire type) (Standard
code model)
Product with the RS-485 communication
port (4-wire type/2-wire type) specified in
-
With "/C4"
the E4 terminal area option (Detailed code
model)
8.3 Connection Diagram
* 1
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
UT75A
Pin No.
Pin No.
501
1
502
2
504
4
505
5
503
3
Remark
8 - 15