Got Side Settings - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

7.2.5

GOT side settings

Setting communication interface
(Communication settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: YOKOGAWA
• Controller Type: YOKOGAWA STARDOM/FA500/
FA-M3
• I/F: Interface to be used
• Driver: YOKOGAWA FA500/FA-M3/STARDOM
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
7.2.5■Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
7 - 8
7. CONNECTION TO YOKOGAWA PLC
7.2 Serial Connection
Click!
[Controller Setting] from the
Communication detail settings
Make the settings according to the usage environment.
3.
4.
Item
Set this item when change the
transmission speed used for
Transmission
communication with the connected
Speed
equipment.
(Default: 9600bps)
Set this item when change the data length
used for communication with the
Data Bit
connected equipment.
(Default: 8bits)
Specify the stop bit length for
Stop Bit
communications.
(Default: 1bit)
Specify whether or not to perform a parity
check, and how it is performed during
Parity
communication.
(Default: No)
Set whether or not to perform a sum check
Sum Check
during communication.
(Default: Yes)
Set the number of retries to be performed
when a communication timeout occurs.
Retry
When receiving no response after retries,
the communication times out.
(Default: 0time)
Set the time period for a communication to
Timeout Time
time out.
(Default: 3sec)
Set this item to adjust the transmission
timing of the communication request from
Delay Time
the GOT.
(Default: 0ms)
POINT
POINT
POINT
(1) Communication interface setting by the Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
GOT2000 Series User's Manual (Utility)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
Description
4800bps,
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
Yes or No
0 to 5times
1 to 30sec
0 to 300(ms)
Range