Connecting To Ag500 - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

9.5.10 Connecting to AG500

Communication settings
Make the communication settings by operating the key
of the temperature controller.
Item
*1
9600bps, 19200bps, 38400bps
Communication speed
Communication protocol
MODBUS
[8N1]: 8bit, None, 1bit
[8N2]: 8bit, None, 2bit
*1
Data bit configuration
[8E1]: 8bit, Even, 1bit
(Data bit, Parity bit, Stop
[8E2]: 8bit, Even, 2bit
bit)
[8O1]: 8bit, Odd, 1bit
[8O2]: 8bit, Odd, 2bit
*2
Device address
*4
1 to 99
(Slave address)
*3
0 to 250 (ms)
Interval time
*1
Adjust the settings with GOT settings.
*2
Select the device address1 without overlapping with that of
other units.
*3
Set the maximum time from the sending of the last character
stop bit from the GOT side until the switching of the GOT
side to the receiving status (until the temperature controller
becomes ready to send). Set as necessary.
*4
When the setting value is set to 0, a communication is not
made.
9.5.11
Connecting to RMC500
Communication settings
Make the communication settings by operating the key
of the temperature controller.
Item
*1
9600bps, 19200bps, 38400bps
Communication speed
Communication protocol
MODBUS
MODBUS data
*2
0 to 255 (ms)
Extension time
[8N1]: 8bit, None, 1bit
[8N2]: 8bit, None, 2bit
*1
Data bit configuration
[8E1]: 8bit, Even, 1bit
(Data bit, Parity bit, Stop
[8E2]: 8bit, Even, 2bit
bit)
[8O1]: 8bit, Odd, 1bit
[8O2]: 8bit, Odd, 2bit
*3
Device address
*4
1 to 99
(Slave address)
*5
0 to 250 (ms)
Interval time
*1
Adjust the settings with GOT settings.
*2
Set the extension time for the data interval time in the
MODBUS communication (which is lower than 24 bit time).
Set when the data time interval exceeds 24 bit time.
*3
Select the device address without overlapping with that of
other units.
*4
When the setting value is set to 0, a communication is not
made.
*5
Set the maximum time from the sending of the last character
stop bit from the GOT side until the switching of the GOT
side to the receiving status (until the temperature controller
becomes ready to send). Set as necessary.
Setting range
Setting range
9. CONNECTION TO RKC TEMPERATURE CONTROLLER
9.5.12 Connecting to MA900, MA901
Communication settings
Make the communication settings by operating the key
of the temperature controller.
Item
*1
9600bps, 19200bps
Communication speed
[8N1]: 8bit, None, 1bit
[8N2]: 8bit, None, 2bit
*1
Data bit configuration
[8E1]: 8bit, Even, 1bit
(Data bit, Parity bit, Stop
[8E2]: 8bit, Even, 2bit
bit)
[8O1]: 8bit, Odd, 1bit
[8O2]: 8bit, Odd, 2bit
*2
Device address
*4
1 to 99
(Slave address)
*3
0 to 250 (ms)
Interval time
*1
Adjust the settings with GOT settings.
*2
Select the device address1 without overlapping with that of
other units.
*3
Set the maximum time from the sending of the last character
stop bit from the GOT side until the switching of the GOT
side to the receiving status (until the temperature controller
becomes ready to send). Set as necessary.
*4
When the setting value is set to 0, a communication is not
made.
9.5.13 Connecting to THV-A1
Communication settings
Make the communication settings by operating the key
of the temperature controller.
Item
*1
9600bps (fixed)
Communication speed
Data bit: 8bit (fixed)
*1
Parity bit: None (fixed)
Data bit configuration
Stop bit: 1bit (fixed)
*2
Device address
*4
1 to 99
(Slave address)
*3
0 to 250 (ms)
Interval time
*1
Adjust the settings of the GOT side with the temperature
controller settings.
*2
Select the device address1 without overlapping with that of
other units.
*3
Set the maximum time from the sending of the last character
stop bit from the GOT side until the switching of the GOT
side to the receiving status (until the temperature controller
becomes ready to send). Set as necessary.
*4
When the setting value is set to 0, a communication is not
made.
9.5 Temperature Controller Side Setting