Connecting To Ut100 Series - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

8.5.2

Connecting to UT100 Series

Communication settings
Make the communication settings by operating the key
of the temperature controller.
Item
Transmission speed
9600bps
*1
7bits, 8bits
Data bit
*1
Even, odd, none
Parity bit
*1
1bit, 2bits
Stop bit
*1*2
1 to 99
Address
0: PC link communication (without sum check)
*1
Protocol selection
1: PC link communication (with sum check)
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the address with any of the other units.
8.5.3
Connecting to UT2000 Series
Communication settings
Make the communication settings using setting
switches.
Item
Transmission speed
9600bps
*1
8bits (fixed)
Data bit
*1
Even, odd, none
Parity bit
*1
1bit (fixed)
Stop bit
*1*2
1 to 16
Station No.
Communication mode
PC link communication mode
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the station No. with any of the other
units.
Settings by switch
(1) Settings of the transmission speed and the parity
Make those settings by operating the communication
setting Rotary switch.
Transmission
Switch position
speed
0
1
9600bps
2
8 - 30
8. CONNECTION TO YOKOGAWA TEMPERATURE CONTROLLER
8.5 Temperature Controller Side Setting
Set value
Set value
Communication mode
select DIP SW
Communication setting
Rotary switch
Station No. select
Rotary switch
Parity bit
None
Odd
Even
(2) Communication mode settings
Make this setting by operating the communication
mode select DIP SW.
Switch position
Communication mode
ON
PC link communication mode
(3) A setting of the station No.
Make this setting by operating the station No. select
Rotary switch.
Switch position
Station No.
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
A
11
B
12
C
13
D
14
E
15
F
16
8.5.4
Connecting to UTAdvanced
Series
Communication settings
Make the communication settings by operating the key
of the temperature controller.
Item
*1
9600bps, 19200bps, 38400bps
Transmission speed
*1
7bits, 8bits
Data bit
*1
Even, odd, none
Parity bit
*1
1bit, 2bits
Stop bit
*1*2
1 to 99
Address
*1
0 to 10 (x 10ms)
Minimum response time
0: PC link communication (without sum check)
*1
Protocol selection
1: PC link communication (with sum check)
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the address with any of the other units.
ON
OFF
Set value

Hide quick links:

Advertisement

Table of Contents
loading