11.5 PLC Side Setting

POINT
POINT
POINT
GE PLC
For details of GE PLCs, refer to the following manuals.
GE PLC user's Manual
Model name
Series 90-30
PLC CPU
VersaMaxMicro
IC693CMM311
Communication
Modules
IC697CMM711
11.5.1
Connecting to Series 90-30
Communication settings
Make the communication settings using the
engineering tool.
When making the settings, set [Configuration Mode] on
the [Setting] tab of the engineering tool to "SNP only".
Setting item
*1
Port Mode
*2
Port Type
Data Rate
Flow Control
Parity
Stop Bits
*3
Timeout
*4
Turn Around Delay
*5
SNP ID
*6
Converter Power Consumption
*1
Set to SNP.
*2
Set to Slave.
*3
Set to Long.
*4
Set to 0.
*5
Set within the range of 00 to 31.
When specifying the station No. from 0 to 9, add "0" before
the number and set it as 00 to 09.
*6
Set to 0.(only when connecting to Port2)
Refer to
11.5.1
11.5.2
11.5.3
11.5.4
PLC side setting
SNP
Slave
9600bps, 19200bps
NONE
EVEN, ODD, NONE
1bit, 2bits
Long
0
00 to 31
0
11.5.2 Connecting to VersaMaxMicro
Communication settings
Make the communication settings using the
engineering tool.
Setting item
Data Rate
*6
Bits / Character
Parity
Stop Bits
*1
Port Mode
*2
Port Type
Flow Control
*3
Timeout
*4
Turn Around Delay
*5
SNP ID
*1
Set to the SNP protocol.
*2
Set to Slave.
*3
Set to Long.
*4
Set to 0.
*5
Set within the range of 00 to 31.
When specifying the station No. from 0 to 9, add "0" before
the number and set it as 00 to 09.
*6
Set the same set value for the data length for the GOT and
PLC.
11. CONNECTION TO GE PLC
11.5 PLC Side Setting
PLC side setting
9600bps, 19200bps,
38400bps
7bits, 8bits
EVEN, ODD, NONE
1bit, 2bits
SNP
Slave
NONE
Long
0
00 to 31
11 - 13
11