(b) Setting of the station No.
Make the station No. using RS-485 station No.
switches.
Station No.
0 to 99
(c) Connecting
terminating resistors
Turn ON/OFF the terminating resistor using RS-
485 terminating resistor ON/OFF switch.
ON
(d) Setting of Transmission speed, Stop bit, Data bit,
Parity bit, Initializing method
Make the settings using the character configuration
switches.
Setting item
Set value
1
9600bps
ON OFF ON
Transmission
speed
19200bps
OFF ON
1bit
Stop bit
2bits
7bits
Data bit
8bits
Even
Odd
Parity bit
Done
None
Initializing
By switch
method
Switch No.
2
3
4
5
6
7
8
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Connecting to FFU120B
(1) Communication settings
Make the communication settings using setting
switches.
Item
Command-setting-type start-stop
MODE
synchronization, nonsequence format
*1
9600bps, 19200bps
Transmission speed
*1
8bits or 7bits
Data bit
Even or Odd
*1
Parity bit
Done, None
*1
1bit, 2bits
Stop bit
Initializing method
By switch
*1*2
0 to 99
Station No.
*3
ON or OFF
Terminating resistor
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the station No. with any of the other
units.
*3
Turn ON the terminating switch of a general-purpose
interface module which will be a terminal.
(2) Settings by switch
Make the communication settings using each setting
switch.
MODE switch
RS-485 station No.
switches
Terminator switch
(Front view) (Rear view)
(a) Setting of the MODE
Make the MODE settings using the MODE switch.
MODE
Command-setting-type start-stop
synchronization, nonsequence
format
RS-232C 1:1
Command-setting-type start-stop
synchronization, nonsequence
format
RS-232C 1:1,
and RS-485 1:N
Command-setting-type start-stop
synchronization, nonsequence
format
RS-485 1:N
4. CONNECTION TO FUJI PLC
4.2 Serial connection
Set value
Character configuration
switches
Switch position
1
2
3
4 - 19
4

Hide quick links: