8.4 GOT Side Settings

8.4.1
Setting communication
interface (Communication
settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: YOKOGAWA
• Controller type: YOKOGAWA GREEN/UT100/
UT2000/UTAdvanced
• I/F: Interface to be used
• Driver: YOKOGAWA GREEN/UT100/UT2000/
UTAdvanced
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
8.4.2 Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
3.
4.
Click!
8. CONNECTION TO YOKOGAWA TEMPERATURE CONTROLLER
8.4.2
Communication detail settings
Item
Description
Set this item when change the
transmission speed used for
Transmission
communication with the connected
Speed
equipment.
(Default: 9600bps)
Set this item when change the data
length used for communication with the
Data Bit
connected equipment.
(Default: 8bits)
Specify the stop bit length for
Stop Bit
communications.
(Default: 1bit)
Specify whether or not to perform a parity
check, and how it is performed during
Parity
communication.
(Default: Even)
Set whether or not to perform a sum
Sum Check
check during communication.
(Default: No)
Set the number of retries to be performed
Retry
when a communication error occurs.
(Default: 0time)
Set the time period for a communication
Timeout
to time out.
Time
(Default: 3sec)
Specify the host address (station No. of
the GOT to which the temperature
Host Address
controller is connected) in the connected
network.
(Default: 1)
Set this item to adjust the transmission
timing of the communication request from
Delay Time
the GOT.
(Default: 5ms)
Select the communication format.
(Default: 1)
Format 1:
Accessible to GREEN/UT100/UT2000/
Format
UTAdvanced Series
Format 2:
Accessible to GREEN/UT2000/
UTAdvanced Series, Not accessible to
UT100 Series.

8.4 GOT Side Settings

Range
4800bps,
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
8
7bits/8bits
1bit/2bits
None
Even
Odd
Done, None
0 to 5times
1 to 30sec
1 to 99
0 to 300ms
1/2