4.4.1

FUJI MICREX-F Series

Device name
I/O relay (B)
Auxiliary relay (M)
Keep relay (K)
*1
Special relay (F)
Annunciator relay
(A)
Differential relay (D)
Link memory (L)
Timer output
(0.01s) (T)
Timer output
(0.1s) (T)
Counter output (C)
Specified bit of the following
*5
Word device bit
I/O relay (WB)
Auxiliary relay (WM)
Keep relay (WK)
*1
Special relay (WF)
Annunciator relay
(WA)
Differential relay
(WD)
Link memory (WL)
Direct access
W24:0000 to W24:0255
*6*7
(W24)
*4*6*7
User file (W30)
*4*6*7
User file (W31)
W30:0000 to W30:4095
:
W31:0000 to W31:4095
User file
W108:0000 to W108:4095
*4*6*7
(W108)
W109:0000 to W109:4095
User file
*4*6*7
(W109)
Data memory
*2
(BD)
Timer set value
*2*3
(0.01s) (TS)
Timer current value
*2*3
(0.01s) (TR)
Timer current value
W9:0000 to W9:0487
*2*3
(0.1s) (W9)
Counter set value
*2*3
(CS)
Counter current
*2*3
value (CR)
*1
Only reading is possible.
*2
Only 32-bit (2-word) designation is allowed.
4 - 28
4. CONNECTION TO FUJI PLC
4.4 Device Range that Can Be Set
Device No.
Setting range
representation
B0000 to B511F
M0000 to M511F
K0000 to K063F
F0000 to F125F
Decimal +
Hexadecimal
A0000 to A045F
D0000 to D063F
L0000 to L511F
T000 to T511
Decimal
T512 to T999
C000 to C511
word devices
Direct access,
user file
WB000 to WB511
WM000 to WM511
WK000 to WK063
Decimal
WF000 to WF125
WA000 to WA045
WD000 to WD063
WL000 to WL511
Decimal
:
BD0 to BD4095
Decimal
TS0 to TS511
TR0 to TR511
CS0 to CS511
CR0 to CR511
*3
Decimal points are not displayed.
*4
To read/write data from/to a user file, set SI data for the data
format of the PLC CPU and 16 bits for data length on GT
Designer3.
With any setting other than the above, the PLC does not
operate normally.
Data format of the PLC
CPU
SI (Binary 16-bit length)
DI (Binary 32-bit length)
BD (8-digit BCD)
*5
As bit specification of a word device is performed after the
GOT reads the value, do not change the value in the
sequence program during this period.
*6
When it is used with bit specification (bit specification of word
device), the offset function cannot be used.
*7
When bit specification (bit specification of word device) is
performed, the uppermost bit is b0 and the lowermost bit is
b15.
Higher
b0
b1
4.4.2
FUJI MICREX-SX Series
Device name
Setting range
Specified bit of the following
word devices
*1
Word device bit
Direct access,
Non-retain
M0 to M2097151
*2*3
memory(M)
Retain memory
L0 to L2097151
*2*3
(L)
System memory
SM0 to SM511
*2*3
(SM)
*1
As bit specification of a word device is performed after the
GOT reads the value, do not change the value in the
sequence program during this period.
*2
When it is used with bit specification (bit specification of word
device), the offset function cannot be used.
*3
When bit specification (bit specification of word device) is
performed, the uppermost bit is b0 and the lowermost bit is
b15.
Higher
b0
b1
GT Designer3 setting
Device data bit: 16 bits
Cannot be used
Cannot be used
Lower
..........
b14
b15
Device No.
representation
User file
Decimal
Lower
..........
b14
b15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents