10.3.3 GOT Side Settings

Setting communication interface
(Communication settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: AB
• Controller Type: Depends on Ethernet connection
type.
EtherNet/IP (AB): AB Control/CompactLogix
EtherNet/IP (AB Tag): AB Control/CompactLogix
(Tag)
• I/F: Interface to be used
• Driver: Depends on Ethernet connection type.
EtherNet/IP (AB): EtherNet/IP (AB), Gateway
EtherNet/IP (AB Tag): EtherNet/IP (AB Tag),
Gateway
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
■ Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
10 - 16
10. CONNECTION TO ALLEN-BRADLEY PLC
10.3 Ethernet Connection
Click!
[Controller Setting] from the
Communication detail settings
Make the settings according to the usage environment.
3.
4.
Item
GOT Net No.
*1
GOT Station
GOT Ethernet
Setting
GOT
Communication
Port No.
Retry
Startup Time
Timeout Time
Delay Time
*1
Each of [GOT Station] set in the communication detail setting
and [Station] set in the Ethernet setting must be set to
different station numbers.
*2
A default is 5028 when communication drivers are [EtherNet/
IP (AB Tag) , Gateway].
Description
Set the network No. of the GOT.
(Default: 1)
Set the station No. of the GOT.
(Default: 1)
Set the GOT IP address, subnet
mask, default gateway, peripheral S/
W communication port No.,
transparent port No.
Set the GOT port No. for the
connection with the Ethernet module.
*2
(Default: 5026
)
Set the number of retries to be
performed when a communication
timeout occurs.
When receiving no response after
retries, the communication times out.
(Default: 3times)
Specify the time period from the GOT
startup until GOT starts the
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a
communication to time out.
(Default: 3sec)
Set the delay time for reducing the
load of the network/destination PLC.
(Default: 0ms)
Ethernet setting
Range
1 to 239
1 to 64
GOT
Ethernet setting
1024 to 5010,
5014 to 65534
(Except for 5011,
5012, 5013, 44818
and 49153)
0 to 5times
1 to 255sec
3 to 90sec
0 to 10000 (ms)