12.4 GOT Side Settings

12.4.1 Setting communication
interface (Communication
settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: LS Industrial Systems
• Controller Type: LS Industrial Systems MASTER-K
• I/F: Interface to be used
• Driver: LS Industrial Systems MASTER-K
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
12.4.2 Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
Make the settings according to the usage environment.
3.
4.
Transmission
Speed
Data Bit
Stop Bit
Click!
Parity
Retry
Timeout Time
Host Address
Delay Time
POINT
POINT
POINT
12. CONNECTION TO LS INDUSTRIAL SYSTEMS PLC
12.4.2 Communication detail settings
Item
Description
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 38400bps)
Set this item when change the data
length used for communication with
the connected equipment.
(Default: 8bits)
Specify the stop bit length for
communications.
(Default: 1bit)
Specify whether or not to perform a
parity check, and how it is performed
during communication.
(Default: None)
Set the number of retries to be
performed when a communication
error occurs.
(Default: 3times)
Set the time period for a
communication to time out.
(Default: 3sec)
Specify the host address (station No.
of the PLC to which the GOT is
connected) in the network of the
GOT.
(Default: 0)
Set this item to adjust the
transmission timing of the
communication request from the
GOT.
(Default: 0ms)
(1) Communication interface setting by the Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
GOT2000 Series User's Manual (Utility)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
12.4 GOT Side Settings
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
0 to 5times
3 to 30sec
0 to 31
12
0 to 300 (ms)
12 - 11