GOT Ethernet setting
Item
Description
GOT IP
Set the IP address of the GOT.
Address
(Default: 192.168.0.18)
Set the subnet mask for the sub
network.(Only for connection via
Subnet
router)
Mask
If the sub network is not used, the
default value is set.
(Default: 255.255.255.0)
Set the router address of the
default gateway where the GOT is
Default Gateway
connected.(Only for connection via
router)
(Default: 0.0.0.0)
Periphral S/W
Set the GOT port No. for the S/W
Communication
communication.
Port No.
(Default: 5015)
Set the GOT port No. for the
Transparent Port
transparent function.
No.
(Default: 5014)
7 - 18
7. CONNECTION TO YOKOGAWA PLC
7.3 Ethernet Connection
Range
0.0.0.0 to
255.255.255.255
Host
0.0.0.0 to
Net No.
255.255.255.255
Station
0.0.0.0 to
Type
255.255.255.255
IP address
1024 to 5010,
5014 to 65534
(Except for 5011,
5012, 5013 and
Port No.
49153)
Communication
1024 to 5010,
5014 to 65534
format
(Except for 5011,
5012, 5013 and
49153)
Ethernet setting
Item
Description
The host is displayed.(The host is
indicated with an asterisk (*).)
Set the network No. of the
connected Ethernet module.
(Default: blank)
Set the station No. of the
*3
connected Ethernet module.
(Default: blank)
YOKOGAWA (fixed)
Set the IP address of the
*1
connected Ethernet module.
(Default: blank)
Set the port No. of the connected
*2
Ethernet module.
(Default: 12289)
Select a communication protocol.
*1
(Default: UDP)
*1
Set the same IP address and communication format as
those of the PLC side.
*2
Set the port No. of the host link service used on the PLC
side.
*3
Each of [GOT Station] set in the communication detail setting
and [Station] set in the Ethernet setting must be set to
different station numbers.
Communication detail settings
Set value
1 to 239
1 to 64
YOKOGAWA
(fixed)
PLC side IP
address
12289, 12291
UDP, TCP