(2) DIP switch setting (SW3)
Set the communication speed and the data bit
configuration using the DIP switch (SW3).
Dip switch(SW3)
OFF
Setting item
Set value
1
4800bps
OFF OFF
9600bps
ON OFF
Communication
speed
19200bps OFF ON
38400bps
ON
Data bit:
8 bits,
Parity:
None,
Stop: 2
bits
Data bit:
8 bits,
Parity:
None,
Data bit
Stop: 1 bit
configuration
Data bit:
8 bits,
Parity:
Even,
Stop: 1 bit
Data bit:
8 bits,
Parity:
Odd,
Stop: 1 bit
(3) DIP switch settings (SW4)
Set the communication specifications and the
termination resistor using the DIP switch (SW4).
Dip switch(SW4)
ON
O N
OFF
Setting item
Set value
RS-422A
Communication
specification
setting
RS485
Enable
Termination
resistor setting
Disable
9 - 50
9. CONNECTION TO RKC TEMPERATURE CONTROLLER
9.5 Temperature Controller Side Setting
O N
Switch position
2
3
4
5
6
7
-
ON
-
OFF OFF
-
-
ON OFF
-
-
OFF ON
-
-
ON
ON
-
1
2
3
4
Switch position
1
2
3
OFF
OFF
-
ON
ON
-
-
ON
-
OFF

9.5.18 Station number setting

Set each station number so that no station number
overlaps.
The station number can be set without regard to the cable
connection order. There is no problem even if station
numbers are not consecutive.
Station
No.3
GOT
(1) Direct specification
8
The station number setting range of the temperature
controller side differs from that of the GOT side.
Specify the station No. of the temperature controller to
be changed when setting devices referring the following
table.
Module address
Temperature
controller
H-PCP-J
H-PCP-A
H-PCP-B
Z-TIO
Z-COM
Z-DIO
Z-CT
X-TIO
CB, FB, RB,
PF, AG, HA,
MA, RMC,
THV, SA, SB1
B400
4
Station
Station
No.10
No.1
Examples of station number setting
GOT side
setting of
station
temperature
number
controller side
setting
The GOT side station
0 to F
1 to 16
number setting is the module
(Hexadecimal)
(Decimal)
address setting value +1.
The GOT side station
0 to F
17 to 32
number setting is the module
(Hexadecimal)
(Decimal)
address setting value +17.
The GOT side station
0 to F
33 to 48
number setting is the module
(Hexadecimal)
(Decimal)
address setting value +33.
The GOT side station
1 to 99
2 to 100
number setting is the module
(Decimal)
(Decimal)
address setting value +1.
The GOT side station
1 to 99
1 to 99
number setting is the same
(Decimal)
(Decimal)
as the module address
setting value.
The GOT side station
1 to 99
1 to 99
number is the module
(Decimal)
(Decimal)
address setting value +1 or
+2.
Station
Station
No.15
No.6
Remark