Mitsubishi Electric GOT2000 Series Connection Manual page 219

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(17) RS-485 connection diagram 17)
* 3
GOT side
RDA1(RXD1+)
10
RDB1(RXD1-)
12
SDA1(TXD1+)
6
SDB1(TXD1-)
8
SG
2
RSA(RTS+)
14
CSA(CTS+)
18
RSB(RTS-)
16
CSB(CTS-)
20
NC
1
NC
3
NC
4
SDA2(TXD2+)
5
SDB2(TXD2-)
7
RDA2(RXD2+)
9
RDB2(RXD2-)
11
NC
13
NC
15
NC
17
NC
19
*1
Pin No. of temperature controller differs depending on the model. Refer to the following table.
Signal name
SDB (+)
SDA (-)
RDB (+)
RDA (-)
SG
• For the product condition of UTAdvanced series, refer to the following table.
Model
UT55A
UP55A
*2
Terminating resistor should be provided for a GOT and a temperature controller which will be a terminal.
*3
Set the terminating resistor of GOT side which will be a terminal.
■ Connecting terminating resistors
*4
Connect FG grounding to the appropriate part of a cable shield line.
* 4
GREEN
GREEN
Series
Series
UT/UP/
UT32A/UP35A/UM33A
US
UM
Pin No.
Pin No.
Pin No.
23
21
301
24
22
302
25
23
304
26
24
305
27
25
303
Suffix code
Product
condition
Function
Open network
-
A
B
1 or 2
Other than 3
A
-
2
B
-
8. CONNECTION TO YOKOGAWA TEMPERATURE CONTROLLER
Temperature
controller
* 1
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
Terminating resistor(220Ω 1/4W)
Model of temperature controller
UTAdvanced Series
UT35A/
UT55A (product condition B)/
UT55A (product condition A)/
UP55A (product condition B)
UP55A (product condition A)
Pin No.
407
408
410
411
409
Optional suffix code
Product with the open network port of RS-
-
1
485 communication (4-wire type/2-wire
type)
Product with two RS-485 communication
-
Without "/LP"
ports (4-wire type/2-wire type) and without
the power supply for 24VDC sensor
Product without the additional contact
output points (DO) and with the open
-
1
network port of RS-485 communication (4-
wire type/2-wire type) (Standard code
model)
Product with the RS-485 communication
port (4-wire type/2-wire type) specified in
-
With "/CH3"
the E3 terminal area option (Detailed code
model)
Product with two RS-485 communication
-
-
ports (4-wire type/2-wire type) (Standard
code model)
Product with the RS-485 communication
port (4-wire type/2-wire type) specified in
-
With "/C4"
the E4 terminal area option (Detailed code
model)
8.3 Connection Diagram
Temperature
controller
* 1
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
* 4
* 2
UT75A
Pin No.
Pin No.
501
1
502
2
504
4
505
5
503
3
Remark
8 - 23
8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents