Mitsubishi Electric GOT2000 Series Connection Manual page 374

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(2) Ethernet connection type: OP communication
This section describes the Ethernet setting for the
communication driver SIEMENS OP (Ethernet).
Item
Description
The host is displayed. (The host is
Host
indicated with an asterisk (*).)
Set the network No. of the
Net No.
connected Ethernet module.
(Default: blank)
Set the station No. of the connected
*2
Ethernet module.
Station
(Default: blank)
Type
Set the PLC type to be connected.
Set the IP address of the connected
IP Address
Ethernet module.
(Default: blank)
Port No.
102 (fixed)
Set the Connection No./Rack No. set
Connection
on the PLC side.
*1
No./Rack No.
(Default: 0)
Set the Module Position/Slot No. set
Module
on the PLC side.
Position/Slot
(Default)
*1
S7-200 OP: 0
No.
S7-300/400 OP: 2
Communication TCP (fixed)
*1
Connection No./Rack No. and Module Position/Slot No. are
unnecessary for S7-1200 OP.
*2
Each of [GOT Station] set in the communication detail setting
and [Station] set in the Ethernet setting must be set to
different station numbers.
Communication detail settings
15 - 14
15. CONNECTION TO SIEMENS PLC
15.3 Ethernet Connection
Set value
1 to 239
1 to 254
S7-200 OP
S7-300/400 OP
S7-1200 OP
PLC side IP
address
102 (fixed)
0 to 7
S7-200
OP: 0 to 6
S7-300/400
OP: 0 to 31
TCP (fixed)
IP Filter Setting
To improve security, the GOT 2000 series supports the
IP Filter Setting.
For details on the IP Filter Setting, refer to the following
manual.
GT Designer3 (GOT2000) Help