Vt Terminal Settings (Read/Write Setting) (12 Modules); B90 Function (Read/Write Setting); Terminal Frequency (Read Only); Breaker Failure Current Supervision (Read/Write Grouped Setting) - GE UR Series Manual

Hide thumbs Also See for UR Series:
Table of Contents

Advertisement

CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
"
6F90
...Repeated for Terminal Current 19
"
6F92
...Repeated for Terminal Current 20
"
6F94
...Repeated for Terminal Current 21
"
6F96
...Repeated for Terminal Current 22
"
6F98
...Repeated for Terminal Current 23
"
6F9A
...Repeated for Terminal Current 24

VT Terminal Settings (Read/Write Setting) (12 Modules)

B90
6F9C
Terminal Voltage 1 Ratio
"
6F9E
Terminal Voltage 1 Secondary
"
6F9F
...Repeated for Terminal Voltage 2
"
6FA2
...Repeated for Terminal Voltage 3
"
6FA5
...Repeated for Terminal Voltage 4
"
6FA8
...Repeated for Terminal Voltage 5
"
6FAB
...Repeated for Terminal Voltage 6
"
6FAE
...Repeated for Terminal Voltage 7
"
6FB1
...Repeated for Terminal Voltage 8
"
6FB4
...Repeated for Terminal Voltage 9
"
6FB7
...Repeated for Terminal Voltage 10
"
6FBA
...Repeated for Terminal Voltage 11
"
6FBD
...Repeated for Terminal Voltage 12

B90 Function (Read/Write Setting)

B90
6FC0
B90 Function

Terminal Frequency (Read Only)

B90
6FD0
Terminal Frequency
"
6FD1
Terminal Tracking Frequency
Breaker Failure Current Supervision (Read/Write Grouped Setting) (24 Modules)
B90
7000
Breaker Failure 1 Current Supervision
Function
"
7001
Breaker Failure 1 Current Supervision CT
"
7002
Breaker Failure 1 Current Supervision Amp
Supv Pickup
"
7003
Breaker Failure 1 Current Supervision Amp
Hiset Pickup
"
7004
Breaker Failure 1 Current Supervision Amp
Loset Pickup
"
7005
Reserved (4 items)
"
7009
...Repeated for Breaker Failure 2
"
7012
...Repeated for Breaker Failure 3
"
701B
...Repeated for Breaker Failure 4
"
7024
...Repeated for Breaker Failure 5
"
702D
...Repeated for Breaker Failure 6
"
7036
...Repeated for Breaker Failure 7
"
703F
...Repeated for Breaker Failure 8
"
7048
...Repeated for Breaker Failure 9
"
7051
...Repeated for Breaker Failure 10
"
705A
...Repeated for Breaker Failure 11
"
7063
...Repeated for Breaker Failure 12
"
706C
...Repeated for Breaker Failure 13
UR SERIES – COMMUNICATIONS GUIDE
Range
Units
Step
1 to 24000
:1
0.01
50 to 240
V
0.1
0 to 1
---
1
2 to 90
Hz
0.01
2 to 90
Hz
0.01
0 to 1
---
1
0 to 23
---
1
0.001 to 30
pu
0.001 F001
0.001 to 30
pu
0.001 F001
0.001 to 30
pu
0.001 F001
0 to 65535
---
1
MEMORY MAP
Format
Default
F060
1
F001
664
F250
0 (Logic)
F001
0
F001
0
F102
0 (Disabled)
F400
0
1050
1050
1050
F001
0
2-93
2

Hide quick links:

Advertisement

Table of Contents
loading