SCL LOG MESSAGES
CHAPTER 3: IEC 61850 COMMUNICATION
Error creating GOOSE control: GoCBRef too long.
This message is logged when the GOOSE control block reference string is longer than supported.
Error creating GOOSE control: DatSet too long.
This message is logged when the string of dataset reference is longer than supported.
Error creating GOOSE control: GoID too long.
This message is logged when GoID is longer than supported.
Error creating GOOSE control: numDataEntry=<number of data items> not allowed.
This message is logged when the number of dataitems in a dataset is zero.
3
Cannot find runtime type for type id=<type id of dataitem>
This message is logged when unable to find the dataitem with data type in the GCB.
gse_iec_data_init failed for type id=<type is of dataitem>
This message is logged when a dataitem with data type cannot be initialized.
Number of ExtRef elements = <ExtRefs count>. Number of successful GOOSE Subscriptions = <subscriptions
count>
This message is informational.
ERROR: GGIO3 missing
This message is logged when the logical node GGIO3 is missing from the local IED, implying errors with the CID file.
Compare with the IID file and look for differences.
ERROR: add extref=<internal address of extRef> input info
This message is logged when the input is not one of the types — a float, boolean, double point status, quality, timestamp —
or if input assignment fails due to configuration error in the CID file.
update_goose_subscription failed
This message is logged on goose subscription configuration failure.
ldHead is missing for AccessPoint=<apName> in IED=<IED name>
This message is logged when logical device cannot be linked to an access point.
iecGoosePubCreateAll: iedName or apName missing
This message is logged when iedName or apName is missing for the publisher IED.
ERROR: VLAN-PRIORITY=<VLAN priority> out of range.
This message is logged when VLAN-PRIORITY > 13.
ERROR: VLAN-ID=<VLAN ID> out of range.
This message is logged when VLANID > 4095.
ERROR: iecGoosePubCreate failed for finding GCB <gcb name> in <logical device instance>/LLN0 in IED <ied
name>
This message is logged when failed to get update time and address of GoEna from @Master/LLN0.