Neutral Instantaneous Overcurrent (Read/Write Grouped Setting); Ground Time Overcurrent (Read/Write Grouped Setting) - GE UR Series Manual

Hide thumbs Also See for UR Series:
Table of Contents

Advertisement

CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
"
5B55
...Repeated for Neutral Time Overcurrent 6
Neutral Instantaneous Overcurrent (Read/Write Grouped Setting) (1, 4, 6, 8, or 12 Modules)
All except B90,
5C00
Neutral Instantaneous Overcurrent 1
C30, N60, T35
Function
"
5C01
Neutral Instantaneous Overcurrent 1 Signal
Source
"
5C02
Neutral Instantaneous Overcurrent 1
Pickup
"
5C03
Neutral Instantaneous Overcurrent 1 Delay 0 to 600
"
5C04
Neutral Instantaneous Overcurrent 1 Reset
Delay
"
5C05
Neutral Instantaneous Overcurrent 1 Block 0 to 4294967295
"
5C07
Neutral Instantaneous Overcurrent 1
Target
"
5C08
Neutral Instantaneous Overcurrent 1
Events
"
5C09
Reserved (8 items)
B30, C60, C70,
5C11
...Repeated for Neutral Instantaneous
D30, D60, F35,
Overcurrent 2
F60, L30, L60,
L90, M60, T60
"
5C22
...Repeated for Neutral Instantaneous
Overcurrent 3
"
5C33
...Repeated for Neutral Instantaneous
Overcurrent 4
B30, C60, C70,
5C44
...Repeated for Neutral Instantaneous
D60, F35, F60,
Overcurrent 5
L90, M60, T60
"
5C55
...Repeated for Neutral Instantaneous
Overcurrent 6
C60, C70, D60,
5C66
...Repeated for Neutral Instantaneous
F35, F60, L90,
Overcurrent 7
M60, T60
"
5C77
...Repeated for Neutral Instantaneous
Overcurrent 8
C70, F35, T60
5C88
...Repeated for Neutral Instantaneous
Overcurrent 9
"
5C99
...Repeated for Neutral Instantaneous
Overcurrent 10
"
5CAA
...Repeated for Neutral Instantaneous
Overcurrent 11
"
5CBB
...Repeated for Neutral Instantaneous
Overcurrent 12
Ground Time Overcurrent (Read/Write Grouped Setting) (1, 2, 4, or 6 Modules)
B30, C60, C70,
5D00
Ground Time Overcurrent 1 Function
D30, D60, F35,
F60, G30, G60,
L30, L60, L90,
M60, T35, T60
"
5D01
Ground Time Overcurrent 1 Signal Source
"
5D02
Ground Time Overcurrent 1 Input
"
5D03
Ground Time Overcurrent 1 Pickup
"
5D04
Ground Time Overcurrent 1 Curve
"
5D05
Ground Time Overcurrent 1 Multiplier
UR SERIES – COMMUNICATIONS GUIDE
Range
Units
Step
0 to 1
---
1
0 to 5
---
1
0 to 30
pu
0.001 F001
s
0.01
0 to 600
s
0.01
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 5
---
1
0 to 1
---
1
0 to 30
pu
0.001 F001
0 to 16
---
1
0 to 600
---
0.01
MEMORY MAP
Format
Default
F102
0 (Disabled)
F167
0 (SRC 1)
1000
F001
0
F001
0
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0
F102
0 (Disabled)
F167
0 (SRC 1)
F122
0 (Phasor)
1000
F103
0 (IEEE Mod
Inv)
F001
100
2-65
2