Hybrid Permissive Over-Reaching Transfer Trip (Hpott_); Line Current Differential (Lindif); Hybrid Pott Data Objects - GE UR Series Manual

Hide thumbs Also See for UR Series:
Table of Contents

Advertisement

MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)

3.5.2.21 Hybrid permissive over-reaching transfer trip (HPOTT_)

This element is instantiated in the following products: D60, L90.
Table 3-40: Hybrid POTT data objects
HPOTT_PSCH1
LNName:
data attribute
data obj.
Op
general
phsA
phsB
phsC
Tr3p
general
3
Tx1
stVal
Tx2
stVal
Tx3
stVal
Tx4
stVal
BlkRef1
setSrcRef
setSrcCB
InRef5
setSrcRef
setSrcCB
InRef8
setSrcRef
setSrcCB
InRef6
setSrcRef
setSrcCB
InRef7
setSrcRef
setSrcCB
InRef1
setSrcRef
setSrcCB
InRef2
setSrcRef
setSrcCB
InRef3
setSrcRef
setSrcCB
InRef4
setSrcRef
setSrcCB

3.5.2.22 Line current differential (LinDif)

This element is instantiated in the following products: L30, L90.
3-52
Prot
LDevice inst:
Type
FC UR Name
ACT
ST HYBRID POTT OP
BOOLEAN
ST HYBRID POTT TRIP A
BOOLEAN
ST HYBRID POTT TRIP B
BOOLEAN
ST HYBRID POTT TRIP C
BOOLEAN
ACT
ST HYBRID POTT TRIP 3P
BOOLEAN
SPS
ST HYBRID POTT TX1
BOOLEAN
SPS
ST HYBRID POTT TX2
BOOLEAN
SPS
ST HYBRID POTT TX3
BOOLEAN
SPS
ST HYBRID POTT TX4
BOOLEAN
ORG
SP HYB POTT SCHEME BLOCK
ObjectReference
SP
ObjectReference
ORG
SP HYB POTT ECHO COND
ObjectReference
SP
ObjectReference
ORG
SP HYB POTT W/I COND
ObjectReference
SP
ObjectReference
ORG
SP GND DIR O/C FWD
ObjectReference
SP
ObjectReference
ORG
SP GND DIR O/C REV
ObjectReference
SP
ObjectReference
ORG
SP HYB POTT RX1
ObjectReference
SP
ObjectReference
ORG
SP HYB POTT RX2
ObjectReference
SP
ObjectReference
ORG
SP HYB POTT RX3
ObjectReference
SP
ObjectReference
ORG
SP HYB POTT RX4
ObjectReference
SP
ObjectReference
CHAPTER 3: IEC 61850 COMMUNICATION
Hybrid Permissive Over-reaching Transfer Trip element
UR element:
Description
HYBRID POTT OP operand
HYBRID POTT TRIP 3P operand
HYBRID POTT TX1 operand
HYBRID POTT TX2 operand
HYBRID POTT TX3 operand
HYBRID POTT TX4 operand
HYB POTT SCHEME BLOCK setting
Reference to the data attribute to input
Source GoCB of input if via GOOSE
HYB POTT ECHO COND setting
Reference to the data attribute to input
Source GoCB of input if via GOOSE
HYB POTT W/I COND setting
Reference to the data attribute to input
Source GoCB of input if via GOOSE
GND DIR O/C FWD setting
Reference to the data attribute to input
Source GoCB of input if via GOOSE
GND DIR O/C REV setting
Reference to the data attribute to input
Source GoCB of input if via GOOSE
HYB POTT RX1 setting
Reference to the data attribute to input
Source GoCB of input if via GOOSE
HYB POTT RX2 setting
Reference to the data attribute to input
Source GoCB of input if via GOOSE
HYB POTT RX3 setting
Reference to the data attribute to input
Source GoCB of input if via GOOSE
HYB POTT RX4 setting.
Reference to the data attribute to input
Source GoCB of input if via GOOSE
UR SERIES – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents