CHAPTER 3: IEC 61850 COMMUNICATION
SynChkRSYN#
LNName:
data attribute
data obj.
Type
DeaV1
SPS
stVal
BOOLEAN
LivV2
SPS
stVal
BOOLEAN
DeaV2
SPS
stVal
BOOLEAN
LivDea
SPS
stVal
BOOLEAN
LivDeaDpo
SPS
stVal
BOOLEAN
LivLiv
SPS
stVal
BOOLEAN
LivLivDpo
SPS
stVal
BOOLEAN
DifVClc
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
zeroDb
INT32U
DifHzClc
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
zeroDb
INT32U
UR SERIES – COMMUNICATIONS GUIDE
Ctrl
LDevice inst:
FC UR Name
ST SYNC # V1 BELOW MAX
ST SYNC # V2 ABOVE MIN
ST SYNC # V2 BELOW MAX
ST SYNC # DEAD S OP
ST SYNC # DEAD S DPO
ST SYNC # SYNC OP
ST SYNC # SYNC DPO
MX
SYNCHROCHECK 1 DELTA VOLT
MX
CF
CF SynChkRSYN#.DifVClc.db
CF
MX
SYNCHROCHECK # DELTA FREQ
multiplied by 100
MX
SYNCHROCHECK # DELTA FREQ
multiplied by 100, on deadband
exception
CF
CF SynChkRSYN#.DifHzClc.db
CF
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Synchrocheck element # (ANSI 25)
UR element:
Description
SYNC # V1 BELOW MAX operand, which
indicates that V1 is below the DeaVal1
setting
SYNC # V2 ABOVE MIN operand, which
indicates that V1 is above the LivVal2
setting
SYNC # V2 BELOW MAX operand, which
indicates that V2 is below the DeaVal1
setting
SYNC # DEAD S OP operand, which
indicates that live/dead conditions have
been met
SYNC # DEAD S DPO operand, which
indicates that live/dead conditions have not
been met
SYNC # SYNC OP operand, which indicates
that both sources are live, and that angle,
frequency and voltage difference and
range conditions have been met
SYNC # SYNC DPO operand, which indicates
that one or both sources are not live, or that
angle, frequency and voltage difference
and range conditions have been met
SYNCHROCHECK # DELTA VOLT, in primary
volts
SYNCHROCHECK # DELTA VOLT,
deadbanded
29, the code for volts
0, the code for a multiplier of 1
SYNCHROCHECK # DELTA FREQ, in Hz
33, the code for hertz (1/s)
0, the code for a multiplier of 1
0
R/W/C
R
R
R
R
R
R
R
3
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R/W/C