CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name

RTD Inputs (Read/Write Setting) (48 Modules)

All except B90
5400
RTD Input 1 Function
"
5401
RTD Input 1 ID
"
5407
RTD Input 1 Type
"
5408
RTD Input 1 Application
"
5409
RTD Input 1 Alarm Temperature
"
540A
RTD Input 1 Alarm Pickup Delay
"
540B
RTD Input 1 Trip Temperature
"
540C
RTD Input 1 Trip Pickup Delay
"
540D
RTD Input 1 Trip Reset Delay
"
540E
RTD Input 1 Trip Voting
"
540F
RTD Input 1 Open
"
5410
RTD Input 1 Block
"
5412
RTD Input 1 Target
"
5413
RTD Input 1 Events
"
5414
...Repeated for RTD Input 2
"
5428
...Repeated for RTD Input 3
"
543C
...Repeated for RTD Input 4
"
5450
...Repeated for RTD Input 5
"
5464
...Repeated for RTD Input 6
"
5478
...Repeated for RTD Input 7
"
548C
...Repeated for RTD Input 8
"
54A0
...Repeated for RTD Input 9
"
54B4
...Repeated for RTD Input 10
"
54C8
...Repeated for RTD Input 11
"
54DC
...Repeated for RTD Input 12
"
54F0
...Repeated for RTD Input 13
"
5504
...Repeated for RTD Input 14
"
5518
...Repeated for RTD Input 15
"
552C
...Repeated for RTD Input 16
"
5540
...Repeated for RTD Input 17
"
5554
...Repeated for RTD Input 18
"
5568
...Repeated for RTD Input 19
"
557C
...Repeated for RTD Input 20
"
5590
...Repeated for RTD Input 21
"
55A4
...Repeated for RTD Input 22
"
55B8
...Repeated for RTD Input 23
"
55CC
...Repeated for RTD Input 24
"
55E0
...Repeated for RTD Input 25
"
55F4
...Repeated for RTD Input 26
"
5608
...Repeated for RTD Input 27
"
561C
...Repeated for RTD Input 28
"
5630
...Repeated for RTD Input 29
"
5644
...Repeated for RTD Input 30
"
5658
...Repeated for RTD Input 31
"
566C
...Repeated for RTD Input 32
UR SERIES – COMMUNICATIONS GUIDE
Range
Units
Step
0 to 1
---
1
---
---
---
0 to 3
---
1
0 to 5
---
1
1 to 249
°C
1
0 to 600
s
0.01
1 to 249
°C
1
0 to 600
s
0.01
0 to 600
s
0.01
0 to 48
---
1
0 to 2
---
1
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
MEMORY MAP
Format
Default
F102
0 (Disabled)
F205
"RTD Ip 1"
F174
0 (100 ohm
Platinum)
F550
0 (None)
F001
130
F001
0
F001
130
F001
0
F001
0
F551
0
F552
0 (None)
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)